161
B
E
E
F
G
H
I
J
K
L
M
N
3.6 Minimum and maximum distances
X/2
X
Y
Unit type
CON-9
Align the RoofVent
®
units so that no unit draws in the
exhaust air from another unit as fresh air.
The extract air grille must be easily accessible.
Provide a clear space of approx. 1.5 m on the side
opposite to the coil connections for service and main-
tenance.
The stream of supply air must be able to spread unob-
structed (note position of beams and lamps).
Unit clearance X
Min.
m
13.0
Max.
m
28.0
Mounting height Y
1)
Min.
1)
m
5.0
Max.
2)
m 14.0 … 16.0
1)
The minimum height can be reduced by 1 m in each case using the 'Air
outlet box' option (see Section K 'Options').
2)
The maximum height varies depending on the ancillary conditions (for
values, see Table G6).
Table G7: Minimum and maximum distances
RoofVent
®
condens
Technical data
Summary of Contents for RoofVent CON-9
Page 2: ......
Page 4: ...2...
Page 6: ...4...
Page 8: ...6...
Page 12: ...10 RoofVent LHW Use...
Page 40: ...38 RoofVent LKW Use...
Page 68: ...66 RoofVent twin heat Use...
Page 94: ...92 RoofVent twin cool Use...
Page 122: ...120 RoofVent twin pump Use...
Page 150: ...148...
Page 154: ...152 RoofVent condens Use...
Page 180: ...210 RoofVent LH Construction and operation...
Page 208: ...238 RoofVent LK Use...
Page 256: ...286...
Page 268: ...298...
Page 274: ...304...
Page 279: ......