95 = C2 check sum failure.
96 =Current decimal points for the C2 value.
PROFIBUS Error Codes
for Rate Calibration
73 =Low rate Calibration percentage High percentage
74 =High rate Calibration percentage out of range
75 =Low rate cal High rate cal
76 = High rate Calibration percentage out of range
77 =Negative values not allowed
78 =Feed Time out of range
HI 2160RC
PLUS
Error
Messages
NOTE:
These messages appear in the display when an error occurs.
MESSAGE
SUB-MENU
DESCRIPTION
!!MOTION!!
CALIBRATION
1. Scale is in motion while entering the Zero or
Span Value.
2. Zero or Span value is trying to be entered
before the controller has accumulated and
averaged 200 readings. When calibrating
the scale, feeder and agitator motors must
be off and you must wait at least 12 seconds
before entering Zero and Span.
3. Remove the source of the scale motion and
then re-calibrate Zero and Span.
4. Too many decimal points selected.
MAXIMUM = 100
TUNING/CONTROL
Control output HI (%) or Control Output LO (%)
value was more than 100%. Enter a value of
100% or lower.
MAXIMUM = 200
TUNING/CONTROL
Value entered for Averages was more than 200.
Enter a value of 200 or lower.
MAXIMUM = 999
TUNING/CONTROL
Value entered for Timebase was more than 999.
Enter a value of 999 or lower.
Summary of Contents for HI 2160RC PLUS
Page 1: ...HI 2160RCPLUS Rate Controller Operation and Installation Manual ...
Page 23: ...HI 2160RCPLUS MANUAL 2 6 ...
Page 49: ...HI 2160RCPLUS MANUAL 3 26 ...
Page 67: ...HI 2160RCPLUS MANUAL 4 18 ...
Page 91: ...HI 2160RCPLUS MANUAL 5 24 ...
Page 151: ...HI 2160RCPLUS MANUAL 7 12 ...
Page 187: ...HI 2160RCPLUS MANUAL 8 36 ...
Page 207: ...HI 2160RCPLUS MANUAL 9 20 ...
Page 219: ...Data Worksheets WKSHT 6 ...