Step 6. Setting a Percentage of the HI Output Signal. (See Fig. 8-24)
•
The HI 2160RC
PLUS
Percentage Function allows the oper-
ator to quickly change the HI Output Signal in order to
reduce the flow rate, without changing the HI Output Sig-
nal. For Example:
The HI output signal setting is 10.00 LBS/MIN. The pro-
cess slows down and the feed rate required is only 9 LBS/
MIN. You can set the Set Point Percentage at 90% of the
HI output signal and the HI 2160RC PLUS slows the
feeder rate to 9 LBS/MIN. If the process requires 5.7
LBS/MIN, set the percentage for 57%, 6.3 LBS/MIN, set
the percentage for 63%, etc.
•
Press the Config button. The Main Menu appears.
•
Press the down arrow
↓
until the cursor is to the left of the
Remote Set Point sub-menu.
•
Press the Enter button. The Set Point Menu appears with
the cursor next to the Percentage sub-menu. (See Fig. 8-
25)
•
Press the Clear button to clear the value. A setting of 0.00
= 100% output signal.
•
Use the numeric keys to enter the new percentage parame-
ter.
•
Press the Enter button to accept the new percentage.
Step 7. Setting the Set Point Low (SPL) parameter. (See Fig. 8-25)
REMOTE SETPOINT MENU
AVERAGES (1 -20) 20
SPL 1 .000 LBS/MIN
SPH 2.000 LBS/MIN
FIG. 8-26 REMOTE SETPOINT MENU/SETTIN SPL & SPH
Summary of Contents for HI 2160RC PLUS
Page 1: ...HI 2160RCPLUS Rate Controller Operation and Installation Manual ...
Page 23: ...HI 2160RCPLUS MANUAL 2 6 ...
Page 49: ...HI 2160RCPLUS MANUAL 3 26 ...
Page 67: ...HI 2160RCPLUS MANUAL 4 18 ...
Page 91: ...HI 2160RCPLUS MANUAL 5 24 ...
Page 151: ...HI 2160RCPLUS MANUAL 7 12 ...
Page 187: ...HI 2160RCPLUS MANUAL 8 36 ...
Page 207: ...HI 2160RCPLUS MANUAL 9 20 ...
Page 219: ...Data Worksheets WKSHT 6 ...