HOST PLC
HOST COMPUTER
HI 2160RC
#01
PLUS
HI 2160RC
#02
PLUS
HI 2160RC
#032
PLUS
HI 2151/30
#031
HI 2160RC
PLUS
MANUAL
7-2
FIG. 7-1 MULTIDROP CONFIGURATION WITH HOST AND
CONTROLLERS
NOTE:
The 2100 Series batch, rate and weight controllers are intelligent front ends to a dis-
tributed system, therefore, network speed is normally is not critical.
Serial Commands
•
Serial commands are transmitted to the instrument in ASCII format.
Each command has a single letter corresponding to the command.
•
The instrument accepts command strings up to 40 characters (the
40th character will internally default to a carriage return).
Serial Command
Lists
1. Set Commands (S)
COMMAND
SUB-
CMD
DATA
FORMAT
DESCRIPTION OF COMMAND
S
AH
XXXXXX
Set Auto Refill HI Shutoff (up to 6 digits; include decimal point if used).
S
AI
Y OR N
Set Initial Fill (Y for ON; N for OFF).
S
AL
XXXXXX
Set Auto Refill LO Shutoff (up to 6 digits; include decimal point if used.)
S
AP
XXXXXX
Set Auto Refill Stop Level (up to 6 digits; include decimal point if used.)
S
AR
XXXXXX
Set Auto Refill Start Level (up to 6 digits; include decimal point if used.)
TABLE 7-1: S (SET) COMMANDS LISTED ALPHABETICALLY WITHIN SUB-COMMAND
Summary of Contents for HI 2160RC PLUS
Page 1: ...HI 2160RCPLUS Rate Controller Operation and Installation Manual ...
Page 23: ...HI 2160RCPLUS MANUAL 2 6 ...
Page 49: ...HI 2160RCPLUS MANUAL 3 26 ...
Page 67: ...HI 2160RCPLUS MANUAL 4 18 ...
Page 91: ...HI 2160RCPLUS MANUAL 5 24 ...
Page 151: ...HI 2160RCPLUS MANUAL 7 12 ...
Page 187: ...HI 2160RCPLUS MANUAL 8 36 ...
Page 207: ...HI 2160RCPLUS MANUAL 9 20 ...
Page 219: ...Data Worksheets WKSHT 6 ...