Chapter 6 - Setup
6-25
•
The default settings are:
•
Auto Refill
NO
•
START (LO)
2.000
•
STOP (HI)
40.000
•
LO SHUTOFF
1.000
•
HI SHUTOFF
50.000
•
Initial Fill
YES
•
RFL CORR
0.0
Selecting the
Auto Refill
Function
NOTE:
The Rate Exception Control must be turned on when enabling the automatic refill.
Step 1. Press the Config button and enter the Main Menu.
Step 2. Press the down arrow
↓
button until the cursor is to the left of
the AUTO REFILL Sub-Menu.
Step 3. Press the Enter button. The AUTO REFILL Menu appears.
(See Fig. 6-19)
A U T O R E F I L L M E N U
A u t o R e f i l l N O
S TA R T ( L O ) 2 . 0 0 0
S T O P ( H I ) 4 0 . 0 0 0
FIG. 6-19 AUTO REFILL MENU/START AND STOP SETTINGS
Step 4. Press the down arrow
↓
button until the cursor is to the left of
the AUTO REFILL Sub-Menu.
Step 5. Press the Select button to select YES.
Step 6. Press the Enter button to accept the selection.
NOTE:
When setting the START limit, make sure that the limit is adequate to allow the opera-
tor or the system plenty of time to begin filling the feeder before the feeder runs out of
material. Conversely, when setting the STOP limit, make sure that the limit is ade-
Summary of Contents for HI 2160RC PLUS
Page 1: ...HI 2160RCPLUS Rate Controller Operation and Installation Manual ...
Page 23: ...HI 2160RCPLUS MANUAL 2 6 ...
Page 49: ...HI 2160RCPLUS MANUAL 3 26 ...
Page 67: ...HI 2160RCPLUS MANUAL 4 18 ...
Page 91: ...HI 2160RCPLUS MANUAL 5 24 ...
Page 151: ...HI 2160RCPLUS MANUAL 7 12 ...
Page 187: ...HI 2160RCPLUS MANUAL 8 36 ...
Page 207: ...HI 2160RCPLUS MANUAL 9 20 ...
Page 219: ...Data Worksheets WKSHT 6 ...