Chapter 9 - Torubleshooting and Repair
9-11
FIG. 9-6 JUMPER SETTINGS FOR CONTROL OUTPUT CARD
TROUBLE
PROBABLE CAUSE
REMEDY
When pushing the Start
button it does not acti-
vate the motor controller
(Analog Control) on the
feeder.
4.
Batch Set Point Amount
is set too low.
5.
Control Out HI (%) is set
too low. “NOT
ALLOWED” statement
appears, preventing the
feeder motor from start-
ing.
4. Raise the Batch Set
Point Amount Setting.
If the batch set point is
too low the instrument
does not have time to
see it and thinks it has
already met or
exceeded the condi-
tion. (See Chapter 7
for instructions.
5. Raise the Control Out
HI (%). the CTL Out HI
(%) setting is located
in the Tuning/control
Sub-Menu. (See
Chapter 5 for instruc-
tions)