PLC
HI 2160RC #1
HI 2160RC #2
HI 2160RC #3
4-20 mA Analog Output Signal from PLC
Relay Output from PLC to
HI 2160RC Remote Relay
Relay Output from PLC to
HI 2160RC Ground
I
P
Analog Signal
From PLC Analog
Module
Analog Signal
To HI 2160RC #1
Set Point Option
PC Board
Analog Signal
To HI 2160RC #2 & #3
Set Point Option
PC Board
Chapter 8 - Operation
8-27
FIG. 8-27 ANALOG SIGNAL CONFIGURATION DIAGRAM
Step 9. The remote set point is set for 4-20 mA and a single analog
output from the PLC controls all three HI 2160RC
PLUS
s.
Step 10. Downloading Set Points (See Fig. 8-27 & 8-28))
•
Download the set point information to the 4-20 milliamp
output line.
•
Close the Relay for the selected controller, in this case HI
2160RC
PLUS
#1
•
Open the Relay for the selected controller, in this case HI
2160RC
PLUS
#1.
•
The set point is downloaded.
Step 11. To download the set point information for the other control-
lers, (up to sixteen (16) per relay module) repeat Download-
ing Set Points above.