Order No. 2104 ..
Function:
Command value
Object
h
42
Function
Command value for
heating/cooling / basic level
Name
C.Output
Type
1-bit
DPT
1,001
Flag
C, -, T, (R)
1
Description
1-bit object to output the combined switching command value of the heating
and cooling mode. In two-level heating/cooling mode, command value output
for the basic level This object is only available in this way if the command
values for heating and cooling mode are output to a shared object (parameter-
dependent). The type of feedback control must also be configured to
"Switching 2-point feedback control".
Object for command value output, additional heating and combined valve additional
heating/cooling
Function:
Command value
Object
h
43
Function
Command value additional
heating
Name
C.Output
Type
1
bytes
DPT
5,001
Flag
C, -, T, (R)
1
Description
1-byte object to output the continuous command value for additional heating in
two-level operation. This object is only available in this way if the type of
feedback control is configured to "Continuous PI control".
Function:
Command value
Object
h
43
Function
Command value additional
heating (PWM)
Name
C.Output
Type
1-bit
DPT
1,001
Flag
C, -, T, (R)
1
Description
1-bit object to output the continuous PWM command value for additional
heating in two-level operation. This object is only available in this way if the
type of feedback control is configured to "Switching PI control (PWM)".
Function:
Command value
Object
h
43
Function
Command value additional
heating
Name
C.Output
Type
1-bit
DPT
1,001
Flag
C, -, T, (R)
1
Description
1-byte object to output the switching command value for additional heating in
two-level operation. This object is only available in this way if the type of
feedback control is configured to "Switching 2-point feedback control".
Function:
Command value
Object
h
43
Function
Command value additional
level
Name
C.Output
Type
1
bytes
DPT
5,001
Flag
C, -, T, (R)
1
Description
1-byte object to output the combined continuous command value for additional
level in two-level operation. This object is only available in this way if the
command values for heating and cooling mode are output to a shared object
(parameter-dependent). The type of feedback control must also be configured
to "Continuous PI control".
1: Each communication object can be read out. For reading, the R-flag must be set.
Page 29 of 171
Software "KNX CO2 sensor"
Object table