Order No. 2104 ..
-
"Comfort operation" -> The comfort mode will be activated after the initialisation phase.
-
"Standby mode" -> The standby mode will be activated after the initialisation phase.
-
"Night operation" -> The night mode will be activated after the initialisation phase.
-
"Frost/heat protection operation" -> The frost/heat protection mode will be activated after
the initialisation phase.
-
"Restore operation mode before reset" -> The mode set before a reset according to the
operating mode object will be restored after the initializing phase of the device. Operating
modes set by a function with a higher priority before the reset (Forced, Window status,
Presence status) are not effected.
The operating mode objects will be updated after a reset.
i
Note on the "restore operation mode before reset" setting:
Frequent changing of the operating mode (e. g. several times a day) during running
operation can adversely affect the life of the device as the read-only memory (EEPROM)
used has been designed for less frequent write access events only.
Page 86 of 171
Software "KNX CO2 sensor"
Functional description