Order No. 2104 ..
be received via the "Command value
limit" object. The limit can be switched
on or off at any time using the object.
This parameter is only visible with
"Command value limit = can be
activated via object"!
Minimum command
value for heating
(optionally also for basic
and additional level)
5%
, 10%, 15%, 20%, 25%,
30%, 35%, 40%, 45%, 50%
The "Minimum command value"
parameter specifies the lower command
value limiting value for heating. With an
active command value limit, the set
minimum command value is not
undershot by command values. If the
controller calculates smaller command
values, it sets the configured minimum
command value. The controller
transmits a 0 % command value if no
more heating or cooling energy has to
be demanded.
Maximum command
value for heating
(optionally also for basic
and additional level)
55%, 60%, 65%, 70%,
75%, 80%, 85%, 90%,
95%
, 100%
The "Maximum command value"
parameter specifies the upper command
value limiting value for heating. With an
active command value limit, the set
maximum command value is not
exceeded. If the controller calculates
larger command values, it sets the
configured maximum command value.
Minimum command
value for cooling
(optionally control circuit
1)
(optionally also for basic
and additional level)
5%
, 10%, 15%, 20%, 25%,
30%, 35%, 40%, 45%, 50%
The "Minimum command value"
parameter specifies the lower command
value limiting value for cooling. With an
active command value limit, the set
minimum command value is not
undershot by command values. If the
controller calculates smaller command
values, it sets the configured minimum
command value. The controller
transmits a 0 % command value if no
more heating or cooling energy has to
be demanded.
Maximum command
value for cooling
(optionally also for basic
and additional level)
55%, 60%, 65%, 70%,
75%, 80%, 85%, 90%,
95%
, 100%
The "Maximum command value"
parameter specifies the upper command
value limiting value for cooling. With an
active command value limit, the set
maximum command value is not
exceeded. If the controller calculates
larger command values, it sets the
configured maximum command value.
Heating indication
Yes
No
Depending on the set operating mode, a
separate object can be used to signal
whether the controller is currently
Page 131 of 171
Software "KNX CO2 sensor"
Parameters