Order No. 2104 ..
Objects for operating mode change-over
Function:
Operating mode switchover
Object
h
28
Function
Operating mode switchover
Name
C.Input
Type
1
bytes
DPT
20,102
Flag
C, W, T,
(R)
1
Description
1-byte object for change-over of the operating mode of the controller
according to the KNX specification. This object is only available in this way
when the operating mode switchover is to take place over 1 byte (parameter-
dependent).
Function:
Operating mode switchover
Object
h
32
Function
Operating mode forced-
control
Name
C.Input
Type
1
bytes
DPT
20,102
Flag
C, W, T,
(R)
1
Description
1-byte object for forced change-over (highest priority) of the operating mode of
the controller according to the KNX specification. This object is only available
in this way when the operating mode switchover is to take place over 1 byte
(parameter-dependent).
Function:
Operating mode switchover
Object
h
28
Function
Comfort mode
Name
C.Input
Type
1-bit
DPT
1,001
Flag
C, W, T,
(R)
1
Description
1-bit object for change-over to the "Comfort" operating mode. This object is
only available in this way when the operating mode change-over is to take
place over 4 x 1 bit (parameter-dependent).
Function:
Operating mode switchover
Object
h
29
Function
Standby mode
Name
C.Input
Type
1-bit
DPT
1,001
Flag
C, W, T,
(R)
1
Description
1-bit object for change-over to the "Standby" operating mode. This object is
only available in this way when the operating mode change-over is to take
place over 4 x 1 bit (parameter-dependent).
Function:
Operating mode switchover
Object
h
30
Function
Night operation
Name
C.Input
Type
1-bit
DPT
1,001
Flag
C, W, T,
(R)
1
Description
1-bit object for change-over to the "Night" operating mode. This object is only
available in this way when the operating mode change-over is to take place
over 4 x 1 bit (parameter-dependent).
1: Each communication object can be read out. For reading, the R-flag must be set.
Page 23 of 171
Software "KNX CO2 sensor"
Object table