Order No. 2104 ..
button as NC contact)".
Time between two
telegrams,
Base
130 ms
260 ms
520 ms
1 sec
Time base for the time between two
cyclical telegrams during value
adjustment.
Only with "Adjustment via long
actuation? = Yes"!
Time = Basic x Factor
Time between two
telegrams,
Factor (3...127)
3
...127
Time factor for the time between two
cyclical telegrams during value
adjustment.
Only with "Adjustment via long
actuation? = Yes"!
Time = Basic x Factor
Presetting: 520 ms × 3 = 1.56 s
Step width
50 lux
The step width of the adjustment is
permanently set to 50 Lux. Only with
"Adjustment via long actuation? = Yes".
Behaviour after bus
voltage
return
no reaction
Reaction as rising edge
Reaction as falling edge
Transmit current input
status
It is possible to specify which reaction
should take place after bus voltage
return. If a delay after bus voltage return
is configured, this time must first have
elapsed before the pre-set reaction is
executed here.
With "no reaction", no reaction occurs.
With "Reaction as with rising edge", the
value parameterized for the rising edge
will be transmitted.
Only with "Transmit value on = rising
edge (push-button as NO contact)" and
"Transmit value on = rising and falling
edge (switch)"!
With "Reaction as with falling edge", the
value parameterized for the falling edge
will be transmitted.
Only with "Transmit value on = falling
edge (push-button as NC contact)" and
"Transmit value on = rising and falling
edge (switch)"!
With "transmit current input state" the
current input state of the inputs is
transmitted according to the
configuration for the rising and falling
edge.
Page 156 of 171
Software "KNX CO2 sensor"
Parameters