Order No. 2104 ..
protection temperature (default: +7 °C) should be to a set smaller value than the night
temperature. In principle, however, it is possible to select frost protection temperature values
b7.0 °C and +40.0 °C. The possible range of values for a setpoint temperature lies
between +7.0 °C and +99.9 °C for "heating" and is bounded by the frost protection
temperature in the lower range.
The level offset configured in ETS will be additionally considered in a two-level heating mode.
Figure 31: Setpoint temperatures in the operating mode "Basic and additional heating"
T
Comfort setpoint additional level heating
≤ T
Comfort setpoint basic level heating
T
Standby setpoint additional level heating
≤ T
Standby setpoint basic level heating
T
Standby setpoint heating
≤ T
Comfort setpoint heating
or
T
Comfort setpoint additional level heating
≤ T
Comfort setpoint basic level heating
T
Night setpoint additional level heating
≤ T
Night setpoint basic level heating
T
Night setpoint heating
≤ T
Comfort setpoint heating
Setpoints for the "cooling" operating mode
Figure 32: Setpoint temperatures in the operating mode "Cooling"
The setpoint temperatures for comfort, standby and night mode exist for this operating mode.
The heat protection temperature can be preset
The following applies…
Page 89 of 171
Software "KNX CO2 sensor"
Functional description