Order No. 2104 ..
value parameterized for the falling edge
will be transmitted.
Only with "Transmit value on = falling
edge (push-button as NC contact)" and
"Transmit value on = rising and falling
edge (switch)"!
With "transmit current input state" the
current input state of the inputs is
transmitted according to the
configuration for the rising and falling
edge.
Only with "Transmit value on = raising
and falling edge (switch)"!
Value transmitter
function = "Brightness
value transmitter"
Transmit value on
rising edge (push-button
as NO contact)
falling edge (push-button as
NC contact)
rising and falling edge
(switch)
Specifies the edge which starts an
actuation.
Value on rising edge
0...
200
...1500 lux in 50 lux
increments
Setting of the brightness value to be
transmitted.
Only with "Transmit value on = rising
edge (push-button as NO contact)" and
"Transmit value on = rising and falling
edge (switch)"!
Value on falling edge
0
...1500 lux in 50 lux
increments
Setting of the brightness value to be
transmitted.
Only with "Transmit value on = falling
edge (push-button as NC contact)" and
"Transmit value on = rising and falling
edge (switch)"!
Adjustment via long
actuation?
Yes
No
With a long press (< 5 s), the current
value can be cyclically reduced or
increased by the parameterized step
width (see below) and transmitted. After
this value adjustment, the value last
transmitted remains stored.
This parameter defines whether a value
adjustment is possible
Only with "Transmit value on = rising
edge (push-button as NO contact)" and
"Transmit value on = falling edge (push-
Page 155 of 171
Software "KNX CO2 sensor"
Parameters