Order No. 2104 ..
or OFF. Telegrams are not triggered in
this case.
No further evaluation of the limiting
values takes place during the active
frost/heat protection mode. The limiting
values are first evaluated and updated
again after changing to another
operating mode (comfort, standby or
night mode).
If the controller is in the frost/heat
protection operating mode and the
operating mode changes from heating to
cooling or vice versa, then the
parameterised behaviour of the limiting
values is executed according to the
current operating mode of the controller.
The cyclical transmission of the limiting
values of the measured values is not
influenced.
h
Sensor -> CO2 measurement -> Limiting value x (x = 1...4)
Limiting value 1 to 4
(0..2000) * 1ppm
0...
400
...2000
The limiting value can be configured
here.
Hysteresis
(0...50) * 1% related to
limiting value range
0...
5
...50
The hysteresis of the limiting value is
defined by this parameter. The value set
here refers to the limiting value
measuring range (here: 2000 ppm).
External limiting value
1 to 4
No
Absolute value via 2-byte
object
Percentage via 1-byte
object
Save limiting value via
switching obj. (teaching)
With "No" no external limiting value is
configured.
With "Absolute value via 2-byte object"
the limiting value is predefined via a
2-byte value object.
With "Percentage via 1-byte object" the
limiting value is predefined via a 1-byte
value object.
When using the external switching
object "Store limiting value via switching
object", the current measured value of
the sensor can be defined as limiting
value.
Activation of limiting
value
1 to 4
(LV = Limiting value,
Hyst = Hysteresis)
Exceed LV=ON,
undershoot LV-hyst.=OFF
Exceed LV=OFF,
Undershoot LV-hyst.=ON
Undershoot LV=ON,
exceed LV-hyst.=OFF
Determines in which case the limiting
values are activated.
Page 116 of 171
Software "KNX CO2 sensor"
Parameters