Order No. 2104 ..
Function:
Command value
Object
h
47
Function
PWM command value
additional level
Name
C.Output
Type
1
bytes
DPT
5,001
Flag
C, -, T, (R)
1
Description
1-byte object to output the combined continuous command value of a PWM
feedback controller for additional level in two-level operation. This object is
only available in this way if the command values for heating and cooling mode
are output to a shared object (parameter-dependent). The type of feedback
control must also be configured to "Switching PI control (PWM)". In addition to
the switching 1 bit command value of the PWM, the calculated continuous
command value of the controller can also be transmitted to the bus and
displayed, e.g. in a visualisation.
Object for additional command value output, PWM cooling and PWM additional cooling
Function:
Command value
Object
h
48
Function
PWM command value for
cooling / basic cooling
Name
C.Output
Type
1
bytes
DPT
5,001
Flag
C, -, T, (R)
1
Description
1-byte object to output the internal continuous command value of a PWM
feedback controller of the cooling mode. In two-level cooling mode, command
value output for the basic cooling. This object is only available in this way if the
type of feedback control is configured to "Switching PI control (PWM)". In
addition to the switching 1 bit command value of the PWM, the calculated
continuous command value of the controller can also be transmitted to the bus
and displayed, e.g. in a visualisation.
Function:
Command value
Object
h
49
Function
PWM com. value, add.
cooling
Name
C.Output
Type
1
bytes
DPT
5,001
Flag
C, -, T, (R)
1
Description
1-byte object to output the internal continuous command value of a PWM
feedback controller for additional cooling in two-level operation. This object is
only available in this way if the type of feedback control is configured to
"Switching PI control (PWM)". In addition to the switching 1 bit command value
of the PWM, the calculated continuous command value of the controller can
also be transmitted to the bus and displayed, e.g. in a visualisation.
1: Each communication object can be read out. For reading, the R-flag must be set.
Page 33 of 171
Software "KNX CO2 sensor"
Object table