Order No. 2104 ..
Setpoint presetting
relative (setpoint
temperatures from basic
setpoint)
absolute (independent
setpoint temperatures)
It is possible to configure the setpoints
for the "Comfort", "Standby" and "Night"
modes directly (absolute setpoint
presetting) or relatively (derivation from
basic setpoint). This parameter defines
the way the setpoint temperature is
preset.
With "Relative": All temperature
setpoints are derived from the basic
temperature (basic setpoint).
With "Absolute": The setpoint
temperatures are independent of each
other. Different temperature values can
be specified for each operating mode
and heating/cooling mode.
Basic temperature after
reset
(7.0 ... 40.0) * 1°C
7.0...
21.0
...40.0
This parameter defines the temperature
value to be applies as the basic setpoint
after commissioning by the ETS. All the
temperature setpoints are derived from
the basic setpoint.
This parameter is only visible with
relative setpoint presetting!
Value of the setpoint
shift
0.1 K
0.5 K
In addition to presetting individual
temperature setpoints by the ETS or
basic setpoint object, the user, when
presetting relative setpoints, can shift
the basic setpoint in predefined limits
within a specific range. When doing so,
the basic setpoint is adjusted up or
down in levels. The value of a level can
be adjusted here to 0.1 K or 0.5 K.
Permanently apply
change
to basic setpoint shift
No
Yes
In addition to presetting individual
temperature setpoints by the ETS or
basic setpoint object, the user can shift
the basic setpoint in a specific range to
predefined limits. Whether a basic
setpoint shifting only affects the
currently active operating mode or
whether it influences all other setpoint
temperatures of the remaining operating
modes is determined by this parameter.
In the "Yes" setting, the shift of the basic
setpoint carried out affects all operating
modes. The shift is maintained even
after a switchover of the operating mode
or the heating/cooling mode or adjusting
the basic setpoint.
In the "No" setting, the basic setpoint
shift carried out is in effect for only as
long as the operating mode or
heating/cooling mode has not changed
or the basic setpoint is maintained.
Otherwise the setpoint shift will be reset
to "0".
Page 134 of 171
Software "KNX CO2 sensor"
Parameters