Order No. 2104 ..
Transmit current input
status
With "no reaction", no reaction occurs.
With "Reaction as with rising edge", the
value parameterized for the rising edge
will be transmitted.
Only with "Transmit value on = rising
edge (push-button as NO contact)" and
"Transmit value on = rising and falling
edge (switch)"!
With "Reaction as with falling edge", the
value parameterized for the falling edge
will be transmitted.
Only with "Transmit value on = falling
edge (push-button as NC contact)" and
"Transmit value on = rising and falling
edge (switch)"!
With "transmit current input state" the
current input state of the inputs is
transmitted according to the
configuration for the rising and falling
edge.
Only with "Transmit value on = raising
and falling edge (switch)"!
Disable for function
"Brightness value
transmitter"
Disabling function
enabled
disabled
The disabling function can be enabled or
disabled.
Polarity of the disabling
object
Disable = 1 (Enable = 0)
Disable = 0 (Enable = 1)
This parameter sets the polarity of the
disabling object.
Behaviour at the
beginning of the
disabling function
no reaction
Reaction as rising edge
Reaction as falling edge
Transmit current input
status
This parameter determines the reaction
executed at the beginning of the
disabling.
With "no reaction", no reaction occurs.
With "Reaction as with rising edge", the
value parameterized for the rising edge
will be transmitted.
Only with "Transmit value on = rising
edge (push-button as NO contact)" and
"Transmit value on = rising and falling
edge (switch)"!
With "Reaction as with falling edge", the
value parameterized for the falling edge
Page 163 of 171
Software "KNX CO2 sensor"
Parameters