Order No. 2104 ..
4.2.3 Object table
Number of communication objects:
139
(max. object number 138 - gaps in between)
Number of addresses (max):
254
Number of assignments (max):
255
Dynamic table management
no
4.2.3.1 Object table push button interface
Objects of the push button interface
Function:
Switching
Object
h
0, 1
Function
Switching object 1.1
Name
B.Channel 1 / 2
Type
1-bit
DPT
1,001
Flag
C, W, T,
(R)
1
Description
1-bit object for transmission of switching telegrams (ON, OFF, TOGGLE).
Function:
Switching
Object
h
2, 3
Function
Switching object 1.2
Name
B.Channel 1 / 2
Type
1-bit
DPT
1,001
Flag
C, W, T,
(R)
1
Description
1-bit object for transmission of switching telegrams (ON, OFF, TOGGLE).
Function:
Dimming
Object
h
0, 1
Function
Switching
Name
B.Channel 1 / 2
Type
1-bit
DPT
1,001
Flag
C, W, T,
(R)
1
Description
1-bit object for transmission of switching telegrams (ON, OFF, TOGGLE).
Function:
Dimming
Object
h
2, 3
Function
Dimming
Name
B.Channel 1 / 2
Type
4-bit
DPT
3,007
Flag
C, W, T,
(R)
1
Description
4-bit object for the transmission of relative dimming telegrams.
Function:
Venetian blind
Object
h
0, 1
Function
Short time operation
Name
B.Channel 1 / 2
Type
1-bit
DPT
1,007
Flag
C, T (R)
1
Description
1-bit object for the transmission of telegrams with which a Venetian blind or
shutter drive motor can be stopped or with which the blind slats can be
adjusted by short time operation.
1: Each communication object can be read out. For reading, the R-flag must be set.
Page 19 of 171
Software "KNX CO2 sensor"
Object table