10 Basic Troubleshooting
10.1 Start Up and Operation
Symptom
Possible Cause
Test
Solution
Display dark / No function
Missing input power
See
Table 3.1
.
Check the input power source.
Missing or open fuses or circuit
breaker tripped
See open fuses and tripped circuit
breaker in this table for possible
causes.
Follow the recommendations
provided
No power to the keypad
Check the keypad cable for proper
connection or damage.
Replace the faulty keypad or
connection cable.
Shortcut on control voltage
(terminal 12 or 50) or at control
terminals
Check the 24 V control voltage
supply for terminal 12/13 to 20–39
or 10 V supply for terminal 50 to
55.
Wire the terminals properly.
Wrong contrast setting
Press [Status] + [
▲
]/[
▼
] to adjust
the contrast.
Display (keypad) is defective
Test using a different keypad.
Replace the faulty keypad or
connection cable.
Internal voltage supply fault or
SMPS is defective
Contact
supplier.
Intermittent display
Overloaded power supply (SMPS)
due to improper control wiring or
a fault within the adjustable
frequency drive.
To rule out a problem in the
control wiring, disconnect all
control wiring by removing the
terminal blocks.
If the display stays lit, then the
problem is in the control wiring.
Check the wiring for shorts or
incorrect connections. If the display
continues to cut out, follow the
procedure for display dark.
Basic Troubleshooting
AF-600 FP Design and Installation Guide
DET-768A
10-1
10
10
Summary of Contents for AF-600 FP Series
Page 1: ...AF 600 FPTM Fan Pump Drive Design and Installation Guide GE ...
Page 17: ...Introduction AF 600 FP Design and Installation Guide 1 10 DET 768A 1 1 ...
Page 39: ...Start Up and Functional Tes AF 600 FP Design and Installation Guide 3 6 DET 768A 3 3 ...
Page 57: ...About Programming AF 600 FP Design and Installation Guide 5 14 DET 768A 5 5 ...
Page 73: ...Application Set up Examples AF 600 FP Design and Installation Guide 6 16 DET 768A 6 6 ...
Page 83: ...Installation Consideration AF 600 FP Design and Installation Guide 7 10 DET 768A 7 7 ...
Page 87: ...Status Messages AF 600 FP Design and Installation Guide 8 4 DET 768A 8 8 ...
Page 97: ...Warnings and Alarms AF 600 FP Design and Installation Guide 9 10 DET 768A 9 9 ...
Page 101: ...Basic Troubleshooting AF 600 FP Design and Installation Guide 10 4 DET 768A 10 0 ...
Page 103: ...Terminal and Applicable Wir AF 600 FP Design and Installation Guide 11 2 DET 768A 11 1 ...