![background image](http://html.mh-extra.com/html/ge/af-600-fp-series/af-600-fp-series_design-and-installation-manual_17307096.webp)
ALARM 69, Power card temperature
The temperature sensor on the power card is either too
hot or too cold.
Troubleshooting
Check that the ambient operating temperature is
within limits.
Check for clogged filters.
Check fan operation.
Check the power card.
ALARM 70, Illegal adjustable frequency drive configuration:
The control card and power card are incompatible. Contact
your supplier with the model number of the unit from the
nameplate and the part numbers of the cards to check
compatibility.
ALARM 80, Drive initialized to default value
Parameter settings are restored to factory settings after a
manual reset. Reset the unit to clear the alarm.
WARNING 200, Fire mode
This warning indicates the adjustable frequency drive is
operating in Fire mode. The warning clears when fire
mode is removed. See the fire mode data in the alarm log.
WARNING 201, Fire Mode was Active
This indicates the adjustable frequency drive had entered
fire mode. Cycle power to the unit to remove the warning.
See the fire mode data in the alarm log.
WARNING 202, Fire mode limits exceeded
While operating in fire mode one or more alarm conditions
have been ignored which would normally trip the unit.
Operating in this condition voids unit warranty. Cycle
power to the unit to remove the warning. See the fire
mode data in the alarm log.
WARNING 203, Missing motor
With an adjustable frequency drive operating multi-motors,
an underload condition was detected. This could indicate a
missing motor. Inspect the system for proper operation.
WARNING 204, Locked rotor
With an adjustable frequency drive operating multi-motors,
an overload condition was detected. This could indicate a
locked rotor. Inspect the motor for proper operation.
WARNING 250, New spare part
A component in the adjustable frequency drive has been
replaced. Reset the adjustable frequency drive for normal
operation.
WARNING 251, New type code
The power card or other components have been replaced
and the type code changed. Reset to remove the warning
and resume normal operation.
Warnings and Alarms
AF-600 FP Design and Installation Guide
DET-768A
9-9
9
9
Summary of Contents for AF-600 FP Series
Page 1: ...AF 600 FPTM Fan Pump Drive Design and Installation Guide GE ...
Page 17: ...Introduction AF 600 FP Design and Installation Guide 1 10 DET 768A 1 1 ...
Page 39: ...Start Up and Functional Tes AF 600 FP Design and Installation Guide 3 6 DET 768A 3 3 ...
Page 57: ...About Programming AF 600 FP Design and Installation Guide 5 14 DET 768A 5 5 ...
Page 73: ...Application Set up Examples AF 600 FP Design and Installation Guide 6 16 DET 768A 6 6 ...
Page 83: ...Installation Consideration AF 600 FP Design and Installation Guide 7 10 DET 768A 7 7 ...
Page 87: ...Status Messages AF 600 FP Design and Installation Guide 8 4 DET 768A 8 8 ...
Page 97: ...Warnings and Alarms AF 600 FP Design and Installation Guide 9 10 DET 768A 9 9 ...
Page 101: ...Basic Troubleshooting AF 600 FP Design and Installation Guide 10 4 DET 768A 10 0 ...
Page 103: ...Terminal and Applicable Wir AF 600 FP Design and Installation Guide 11 2 DET 768A 11 1 ...