7.1.3 EMC Test Results (Emission)
The following test results were obtained using a system
with an adjustable frequency drive (with options, if
relevant), a shielded control cable, a control box with
potentiometer, as well as a motor and motor-shielded
cable.
RFI filter type
Conducted emission.
Maximum shielded cable length.
Radiated emission
Industrial environment
Housing, trades
and light
industries
Industrial
environment
Housing, trades and light
industries
Standard
EN 55011 Class
A2
EN 55011 Class
A1
EN 55011 Class B
EN 55011 Class A1
EN 55011 Class B
Class A1/B RFI Filter installed
1–60 hp [0.75–45 kW] 200–240
V
500 ft [150 m]
500 ft [150 m]
165 ft [50 m]
Yes
No
1–125 hp [0.75–90 kW] 380–
480 V
500 ft [150 m]
500 ft [150 m]
165 ft [50 m]
Yes
No
Class A2 RFI Filter installed
1–5 hp [0.75–3.7 kW] 200–240
V
16.4 ft [5 m]
No
No
No
No
7.5–60 hp [5.5–45 kW] 200–240
V
82 ft [25 m]
No
No
No
No
1–10 hp [0.75–7.5 kW] 380–480
V
16.4 ft [5 m]
No
No
No
No
15–125 hp [11–90 kW] 380–
480 V
82 ft [25 m]
No
No
No
No
150–1350 hp [110–1000 kW]
380–480 V
500 ft [150 m]
No
No
No
No
150–1600 hp [110–1200 kW]
525–690 V
500 ft [150 m]
No
No
No
No
No RFI Filter installed
1–125 hp [0.75–90 kW] 525–
600 V
-
-
-
-
-
Table 7.3 EMC Test Results (Emission)
7.2 Immunity
Requirements
The immunity requirements for adjustable frequency drives
depend on the environment where they are installed. The
requirements for the industrial environment are higher
than the requirements for the home and office
environment. All GE adjustable frequency drives comply
with the requirements for the industrial environment and
consequently comply also with the lower requirements for
home and office environment with a large safety margin.
In order to document immunity against electrical
interference from electrical phenomena, the following
immunity tests have been made on a system consisting of
an adjustable frequency drive (with options if relevant), a
shielded control cable and a control box with potenti-
ometer, motor cable and motor.
The tests were performed in accordance with the following
basic standards:
•
EN 61000-4-2 (IEC 61000-4-2): Electrostatic
discharges (ESD): Simulation of electrostatic
discharges from human beings.
•
EN 61000-4-3 (IEC 61000-4-3): Incoming electro-
magnetic field radiation, amplitude modulated
simulation of the effects of radar and radio
communication equipment as well as mobile
communications equipment.
•
EN 61000-4-4 (IEC 61000-4-4): Electrical
interference: Simulation of interference brought
about by switching a contactor, relay or similar
devices.
Installation Consideration
AF-600 FP Design and Installation Guide
DET-768A
7-3
7
7
Summary of Contents for AF-600 FP Series
Page 1: ...AF 600 FPTM Fan Pump Drive Design and Installation Guide GE ...
Page 17: ...Introduction AF 600 FP Design and Installation Guide 1 10 DET 768A 1 1 ...
Page 39: ...Start Up and Functional Tes AF 600 FP Design and Installation Guide 3 6 DET 768A 3 3 ...
Page 57: ...About Programming AF 600 FP Design and Installation Guide 5 14 DET 768A 5 5 ...
Page 73: ...Application Set up Examples AF 600 FP Design and Installation Guide 6 16 DET 768A 6 6 ...
Page 83: ...Installation Consideration AF 600 FP Design and Installation Guide 7 10 DET 768A 7 7 ...
Page 87: ...Status Messages AF 600 FP Design and Installation Guide 8 4 DET 768A 8 8 ...
Page 97: ...Warnings and Alarms AF 600 FP Design and Installation Guide 9 10 DET 768A 9 9 ...
Page 101: ...Basic Troubleshooting AF 600 FP Design and Installation Guide 10 4 DET 768A 10 0 ...
Page 103: ...Terminal and Applicable Wir AF 600 FP Design and Installation Guide 11 2 DET 768A 11 1 ...