AF-600 3-
phase
Recommended fuse
size
Recommended max
fuse
[kW]/[HP]
11/15
gG-25
gG-63
15/20
gG-32
18.5/25
22/30
gG-40
30/40
gG-63
gG-80
37/50
gG-100
45/60
gG-80
gG-125
55/75
gG-100
gG-160
75/100
gG-125
90/125
110/150
aR-250
aR-250
132/200
aR-315
aR-315
160/250
aR-350
aR-350
200/300
250/350
aR-400
aR-400
315/450
aR-500
aR-500
400/550
aR-550
aR-550
450/600
aR-700
aR-700
500/650
560/750
aR-900
aR-900
630/900
710/1000
aR-1600
aR-1600
800/1150
900/1250
1000/1350
1200/1600
aR-2000
aR-2000
1400/1900
aR-2500
aR-2500
Table 12.11 525–690 V, IP21/Nema 1 and IP55/Nema 12
Specifications
AF-600 FP Design and Installation Guide
DET-768A
12-19
12
12
Summary of Contents for AF-600 FP Series
Page 1: ...AF 600 FPTM Fan Pump Drive Design and Installation Guide GE ...
Page 17: ...Introduction AF 600 FP Design and Installation Guide 1 10 DET 768A 1 1 ...
Page 39: ...Start Up and Functional Tes AF 600 FP Design and Installation Guide 3 6 DET 768A 3 3 ...
Page 57: ...About Programming AF 600 FP Design and Installation Guide 5 14 DET 768A 5 5 ...
Page 73: ...Application Set up Examples AF 600 FP Design and Installation Guide 6 16 DET 768A 6 6 ...
Page 83: ...Installation Consideration AF 600 FP Design and Installation Guide 7 10 DET 768A 7 7 ...
Page 87: ...Status Messages AF 600 FP Design and Installation Guide 8 4 DET 768A 8 8 ...
Page 97: ...Warnings and Alarms AF 600 FP Design and Installation Guide 9 10 DET 768A 9 9 ...
Page 101: ...Basic Troubleshooting AF 600 FP Design and Installation Guide 10 4 DET 768A 10 0 ...
Page 103: ...Terminal and Applicable Wir AF 600 FP Design and Installation Guide 11 2 DET 768A 11 1 ...