Section 9 - System Programming
9–21
Zones 1-8 can be programmed for any one of the following 24-hour zone types:
24-HOUR ZONES
ZONE TYPE
ZONE OPTIONS
L1, L2
Digits
24-HOUR
ALARM
FIRE
24-HOUR
TROUBLE
AUDIBLE
SILENT
81
9
9
82
9
9
84
9
Always Audible
89
9
9
8A
9
9
24-Hour Zones
FIRE - Fire zones on the system contain Fire Verification Logic. Upon detection of the first
violation, smoke detector power is reset for a period of 8 seconds. After this time period,
power is restored. For 5 seconds the fire zone will not be scanned, allowing the smoke
detectors to settle. Future violations within a 2-minute period will result in a pulsing bell
output, rapid pulsing zone LED, and immediate transmission to the central station. Fire
signals cannot be aborted.
Entry of any valid user code silences the sounder and bell, and resets smoke detector power.
If the system detects that the fire zone is still violated within 2 minutes after power reset,
the zone LED pulses slowly to indicate a fire trouble. Thereafter, smoke detector power is
reset every 4 minutes automatically in an attempt to clear the fire zone.
In the event the fire zone experiences an Open, the system indicates fire trouble by pulsing
the keypad zone LED and sounder slowly. The system Trouble code (followed by the Zone
code) is reported to the central station
The keypad sounder can be silenced through entry of any valid user code.
NOTE: Fire zones cannot be bypassed.
24-HOUR ALARM - This zone type is always active, independent of the system arming
status. Programming options include audible (steady bell) or silent (no bell or keypad
indications). Upon violation, the zone LEDs pulses rapidly (audible zones only) and an
immediate central station transmission occurs which cannot be aborted.
24-Hour Alarm zones can be bypassed; however, they cannot be unbypassed if a violation
exists on the zone terminals.
24-HOUR TROUBLE - This zone type is always active, independent of the system arming
status. Programming options include audible (pulsing keypad sounder) or silent. Upon
violation, the zone LED pulses slowly. Trouble condition must exist for 15 seconds before a
transmission will occur. The keypad display and sounder clears upon zone restoral.
24-Hour Trouble zones can be bypassed; however, they cannot be unbypassed if a violation
exists on the zone terminals.
NOTE: 24-hour Trouble is not to be used for Fire and Burglary Detection zones. 24-Hour
Silent Alarm zones are not to be used for perimeter protection. THE SOUNDER MAY BE
SILENCED THROUGH ENTRY OF ANY VALID USER CODE.
Summary of Contents for Omni-408A
Page 14: ...OMNI 408A Installation and Setup Guide 2 6 ...
Page 22: ...OMNI 408A Installation and Setup Guide 5 4 ...
Page 28: ...OMNI 408A Installation and Setup Guide 6 6 ...
Page 34: ...OMNI 408A Installation and Setup Guide 8 4 ...
Page 76: ...OMNI 408A Installation and Setup Guide 12 2 ...
Page 86: ...OMNI 408A Installation and Setup Guide B 4 ...
Page 88: ...OMNI 408A Installation and Setup Guide C 2 ...
Page 90: ...OMNI 408A Installation and Setup Guide D 2 ...
Page 92: ...OMNI 408A Installation and Setup Guide E 2 ...
Page 95: ......