Section 9 - System Programming
9–25
Question 22, L3 - Trouble Code
Default = F
L3 is the single-digit system Trouble code reported to the central station. This code is
reported on day trouble and fire trouble. If a 2-digit format has been programmed this
code is followed by the second digit of the respective Zone code.
Question 22, L4 - Cancel Code
Default = A
L4 is the single-digit system Cancel code reported to the central station. This code is sent
if a user code is entered after a violation of a controlled zone. If the zone is still violated,
entry of a user code transmits the Cancel code. If the zone is programmed for restoral,
then the Restore code is transmitted when the loop status has returned to normal. Entry
of an “A” in this field indicates that Cancel codes are not transmitted. In formats
requiring 2 digits, the user number functions as the second digit.
QUESTION 23
CS CODES for KEYPAD FIRE and KEYPAD AUXILIARY
DEFAULT = 2AAA
There are 4 locations (L1-L4) in this question:
Question 23, L1 & L2 - Keypad Fire Code
Default = 2A
L1 and L2 are the Alarm code that is transmitted upon activation of the Keypad Fire
condition (pressing the two Fire keys or the [7] [9] keys on the keypad). This code can
vary from any of the zones that are programmed as Fire.
Question 23, L3 & L4 - Keypad Auxiliary Code
Default = AA
L3 and L4 are the code transmitted to the CS for Keypad Aux. condition (pressing the
two Aux. keys or [1] [3] from the keypad).
NOTE: These keypad emergency conditions are optional and can be enabled within question
05 of the programming sequence. If either or both of these transmissions are not desired,
program their respective locations as “AA.”
QUESTION 24
CS CODES RF LOW BATTERY & SUPERVISION
DEFAULT = 1111
There are 4 locations (L1-L4) in this question:
Question 24, L1 - RF Low Battery Code
Default = 1
Question 24, L2 - RF Low Battery Restore
Default = 1
Question 24, L3 - RF Supervisory
Default = 1
Question 24, L4 - RF Supervisory Restore
Default = 1
NOTE: In any question 24 location, if a 2-digit format has been programmed, the second
digit of the respective Zone code follows this code.
QUESTION 25
CS CODES BELL SUPERVISION & TAMPER
DEFAULT = 1A11
There are 4 locations (L1-L4) in this question:
Question 25, L1 & L2 - Bell Supervision Code
Default = 1A
Question 25, L3 - RF Tamper Code
Default = 1
Question 25, L4 - RF Tamper Reset
Default = 1
NOTE: In any question 25 location, if a 2-digit format has been programmed the second digit
of the respective Zone code follows this code.
Summary of Contents for Omni-408A
Page 14: ...OMNI 408A Installation and Setup Guide 2 6 ...
Page 22: ...OMNI 408A Installation and Setup Guide 5 4 ...
Page 28: ...OMNI 408A Installation and Setup Guide 6 6 ...
Page 34: ...OMNI 408A Installation and Setup Guide 8 4 ...
Page 76: ...OMNI 408A Installation and Setup Guide 12 2 ...
Page 86: ...OMNI 408A Installation and Setup Guide B 4 ...
Page 88: ...OMNI 408A Installation and Setup Guide C 2 ...
Page 90: ...OMNI 408A Installation and Setup Guide D 2 ...
Page 92: ...OMNI 408A Installation and Setup Guide E 2 ...
Page 95: ......