Summa Series Servodrive Product Manual
Basic Settings
Document Version: V1.01
(Dec, 2019)
© 2019 ESTUN Automation Co., Ltd. All right reserved.
4-10
Fn000 (Alarm trace data display)
The alarm trace data display can display up to ten previously occurred alarms. The following are the steps
to display the alarm trace data.
Step 1
Press [
M
] key several times to select the Utility Function Mode.
Step 2
Press [▲] key or [▼] key to select the function number Fn000.
Step 3
Press [◄] key to display latest alarm number.
Alarm No.
Sequence
Number
Step 4
Press [▲] key or [▼] key to view the other alarm data.
[
▲
]
[
▼
]
Step 5
Press the [◄] key to return to the display of the Fn000.
Press and hold [◄] key for 1 second or more to clear all the alarm trace data.
Fn001 (Initialize parameter settings)
The following are the steps to initialize parameter settings.
Step 1
Press [
M
] key several times to select the Utility Function Mode.
Step 2
Press [▲] key or [▼] key to select the function number Fn001.
Step 3
Press [◄] key, and Panel Operator displays as below.