Liquiline System CA80HA
Technical data
Hauser
199
PROFINET
Signal encoding
IEEE 802.3 (Ethernet)
Data transmission rate
100 MBd
Galvanic isolation
Yes
Connection
RJ45
Name of station
Via DCP protocol using the configuration tool (e.g. Siemens
PRONETA)
IP address
Via DCP protocol using the configuration tool (e.g. Siemens
PRONETA)
15.2.2 Signal on alarm
Adjustable, as per NAMUR Recommendation NE 43
• In measuring range 0 to 20 mA:
Failure current from 0 to 23 mA
• In measuring range 4 to 20 mA:
Failure current from 2.4 to 23 mA
• Factory setting for failure current for both measuring ranges:
21.5 mA
15.2.3 Load
Max. 500 Ω
15.2.4 Transmission behavior
Linear
15.3 Current outputs, active
15.3.1 Span
0 to 23 mA
15.3.2 Signal characteristic
Linear
15.3.3 Electrical specification
Output voltage
Max. 24 V
Test voltage
500 V
15.3.4 Cable specification
Cable type
Recommended: shielded cable