Example 1: Time-based set point for a temperature controller
The temperature should increase to 21 °C from 08:00 every day, and then to 23 °C for 5 hours
from 12:00. The temperature should be controlled to fall back down to 18 °C from 17.00. Two
time switches are defined for this purpose which are used in a
MF1: Formula
mathematical
function. Using the mathematical function, an analog temperature set point is thus available
for a controller.
T
[° C]
t [h]
18
21
23
8
12
17
0
T2
T1
A0041704
69
Time-based temperature control
1. Program
Time switch 1
(T1):
•
Start date
= 01.01.2020
•
Start time
= 08:00:00
•
Signal duration
= 09:00:00
•
Period
= 24:00:00
2. Define
Time switch 2
(T2):
•
Start date
= 01.01.2020
•
Start time
= 12:00:00
•
Signal duration
= 05:00:00
•
Period
= 24:00:00
3. Create
Formula
mathematical function.
Menu
/
Setup
/
Additional functions
/
Mathematical functions
• MF1: Formula
•
Tracking
=
On
•
Source A
=
Time switch 1
•
Source B
=
Time switch 2
•
Formula
= 18.0 + 3*NUM(A) + 2*NUM(B)