Table 6-4: Error Messages for the Rosemount 5900S
(continued)
Message
Description
Action
Database (Hreg) error
Input register no. 6004.
An error in the transmitter
configuration memory (EEPROM) has
been detected. The error is either a
checksum error that can be solved by
loading the default database or a
hardware error.
Note
The default values are used until the
problem is solved.
The following bits indicate a serious
Holding register problem:
Bit 0: DSP checksum
Bit 1: DSP limit
Bit 2: DSP version
Bit 3: Write error
Load default database and restart the
Rosemount 5900S Radar Level Gauge.
Contact Emerson Automation
Solutions /Rosemount Tank Gauging
service department if the problem
persists.
Other Memory error
Input register no. 6006.
Contact Emerson Automation
Solutions /Rosemount Tank Gauging
service department.
Microwave Module error
Input register no. 6008.
Bit 0: Not connected
RM error
Input register no. 6010
Bit 1: SW configuration
Bit 5: FPROM Checksum
Bit 6: FPROM Version
Bit 9: HREG Checksum
Bit 10: HREG Limit
Bit 11: HREG Write
Bit 12: HREG Read
Bit 13: HREG Version
Bit 14: MWM Invalid Id
Bit 30: SW Serious Error
Other hardware error
Input register no. 6022.
An unspecified hardware error has
been detected.
Bit 0: Internal Temp Out of Range
Reference Manual
Service and troubleshooting
00809-0100-5900
September 2019
Rosemount 5900S Radar Level Gauge
211
Summary of Contents for Rosemount 5900S Series
Page 1: ...Reference Manual 00809 0100 5900 Rev EA September 2019 Rosemount 5900S Radar Level Gauge ...
Page 6: ...Contents Reference Manual September 2019 00809 0100 5900 vi Reference Manual ...
Page 12: ...Introduction Reference Manual September 2019 00809 0100 5900 12 Reference Manual ...
Page 182: ...Configuration Reference Manual September 2019 00809 0100 5900 182 Reference Manual ...
Page 186: ...Operation Reference Manual September 2019 00809 0100 5900 186 Reference Manual ...
Page 266: ...Product Certifications Reference Manual September 2019 00809 0100 5900 266 Reference Manual ...