Table 6-4: Error Messages for the Rosemount 5900S
(continued)
Message
Description
Action
Configuration error
Input register no. 6028.
At least one configuration parameter
is outside allowed range.
Note
The default values are used until the
problem is solved.
Bit 0: Start Code
Bit 1: FF Unit Conversion
•
Load the default database and
restart the level gauge, see
Loading the default database using
TankMaster
.
•
Configure the level gauge or load a
backup configuration file (see
Recover a backup configuration
database using TankMaster
•
Contact Rosemount Tank Gauging
service department if the problem
persists.
Software error
Input register no. 6030.
An error has been detected in the
Rosemount 5900S gauge software.
Bit 0: DSP Undefined SW Error
Bit 1: DSP Task Not Running
Bit 3: Simulated error
Contact Emerson Automation
Solutions /Rosemount Tank Gauging
service department
6.3.4
Measurement status
Measurement Status information can be found by viewing Input register 4002.
presents the various status bits that may appear.
Table 6-5: Measurement Status for the Rosemount 5900S
Message
Description
Action
Full tank
The level measurement is in Full Tank state.
The transmitter waits for the surface echo to
be detected at the top of the tank.
The transmitter leaves the Full Tank state
when the product surface gets below the Full
Tank Detection Area.
Empty tank
The level measurement is in Empty Tank state.
The transmitter waits for the surface echo to
be detected at the bottom of the tank.
The transmitter leaves the Empty Tank state
when the product surface gets above the
Empty Tank Detection Area.
See
.
Dirty antenna
The antenna is so contaminated that the level
measurement might be affected.
Clean the antenna.
Sweep linearization
warning
The sweep is not correctly linearized.
Check Warning messages. If MWM Warning is
active this might indicate a transmitter error.
Contact Emerson Automation Solutions/
Rosemount Tank Gauging service department.
Tank signal clip
warning
The last Tank Signal was clipped.
Check Warning Messages. If MWM Warning is
active this might indicate a transmitter error.
Contact Emerson Automation Solutions/
Rosemount Tank Gauging service department.
No surface echo
The Surface Echo Pulse can not be detected.
Check if the configuration can be changed so
that the surface echo can be tracked in this
current region.
Service and troubleshooting
Reference Manual
September 2019
00809-0100-5900
212
Reference Manual
Summary of Contents for Rosemount 5900S Series
Page 1: ...Reference Manual 00809 0100 5900 Rev EA September 2019 Rosemount 5900S Radar Level Gauge ...
Page 6: ...Contents Reference Manual September 2019 00809 0100 5900 vi Reference Manual ...
Page 12: ...Introduction Reference Manual September 2019 00809 0100 5900 12 Reference Manual ...
Page 182: ...Configuration Reference Manual September 2019 00809 0100 5900 182 Reference Manual ...
Page 186: ...Operation Reference Manual September 2019 00809 0100 5900 186 Reference Manual ...
Page 266: ...Product Certifications Reference Manual September 2019 00809 0100 5900 266 Reference Manual ...