changes to all configurable parameters. The target mode of a block
may be restricted to one or more of the supported modes.
4.11.4
Application example
Level value
A Rosemount 5900S Radar Level Gauge measures the product level in a 15 m high tank.
Table 4-7: Analog Input Function Block Configuration for a Rosemount 5900S Level
Gauge
Parameter
Configured Values
L_TYPE
Direct
XD_SCALE
EU_0=0. EU_100=15. Engineering unit=meter.
OUT_SCALE
EU_0=0. EU_100=15. Engineering unit=meter.
CHANNEL
CH1: Level
4.11.5
Simulation
To perform lab test of process variables and alerts, you can either change the mode of the
AI block to manual and adjust the output value, or you can enable simulation through the
configuration tool and manually enter a value for the measurement value and its status. In
both cases, you must first set the SIMULATE switch (1) on the field device to the ON
position.
With simulation enabled, the actual measurement value has no impact on the OUT value
or the status.
Configuration
Reference Manual
September 2019
00809-0100-5900
142
Reference Manual
Summary of Contents for Rosemount 5900S Series
Page 1: ...Reference Manual 00809 0100 5900 Rev EA September 2019 Rosemount 5900S Radar Level Gauge ...
Page 6: ...Contents Reference Manual September 2019 00809 0100 5900 vi Reference Manual ...
Page 12: ...Introduction Reference Manual September 2019 00809 0100 5900 12 Reference Manual ...
Page 182: ...Configuration Reference Manual September 2019 00809 0100 5900 182 Reference Manual ...
Page 186: ...Operation Reference Manual September 2019 00809 0100 5900 186 Reference Manual ...
Page 266: ...Product Certifications Reference Manual September 2019 00809 0100 5900 266 Reference Manual ...