Air Correction Only
Prior to calibrating and configuring the Verification Pin you will need to set the appropriate
LPG correction method.
Procedure
1. In the Rosemount TankMaster WinSetup work space, select the
Logical View
tab.
2. Select the icon that represents the radar level gauge.
3. Click the right mouse button and select
LPG Setup
to open the
LPG Setup
window:
4. In the
LPG Setup
window click the
Correction
button.
5. Choose
Air Correction Only
from the list of correction methods and click the
OK
button.
This setting is used during the Pin Verification procedure. When the LPG Setup is
finished and the tank is going to be put into operation, the correction method
needs to be changed to a method that applies to the particular type of product that
is used.
Note
The Air Correction Only option shall only be used when the tank atmosphere
contains air and no other gases.