Set the temperature parameter mapping
Rosemount
™
644 temperature transmitters have to be mapped manually in order to
provide input for Vapor Temperature and Average Liquid Temperature calculations.
For Rosemount 2240S Multi-input Temperature Transmitters, temperature readings from
the appropriate elements are automatically mapped to
Vapor Temperature
and
Liquid
Average Temperature
.
The following description shows how to configure Rosemount 644 transmitters as
temperature source devices.
Procedure
1. Choose
Temperature 1
in the
Parameter Mapping
list for the first 644 Temperature
Transmitter. In case there are more than one 644 transmitters on the tank, they will
have to be mapped too: for the second and third 644 transmitter, choose
Temperature 2
and
Temperature 3
in the
Parameter Mapping
list.
Note that the actual Vapor Temperature and Liquid Temperature tank parameters
are not mapped. For example, the resulting Vapor Temperature will be calculated
based on the output from Rosemount 644 transmitters located above the current
product surface.
2. In the
Source Device Type
field, for each temperature parameter (Temperature 1, 2,
3) choose the actual Rosemount 644 transmitter to be used as source device as
illustrated below.
3. In the
Source Parameter
list, choose
Temperature 1
. Note that Temperature 1 is the
source parameter designation for temperature output from a Rosemount 644.
Note
Ensure that temperature element positions are properly configured. This is normally
done in the basic configuration of the Rosemount 5900S level gauge and is required
for proper calculation of Vapor Temperature and Average Liquid Temperature.
Reference Manual
Configuration
00809-0100-5900
September 2019
Rosemount 5900S Radar Level Gauge
119
Summary of Contents for Rosemount 5900S Series
Page 1: ...Reference Manual 00809 0100 5900 Rev EA September 2019 Rosemount 5900S Radar Level Gauge ...
Page 6: ...Contents Reference Manual September 2019 00809 0100 5900 vi Reference Manual ...
Page 12: ...Introduction Reference Manual September 2019 00809 0100 5900 12 Reference Manual ...
Page 182: ...Configuration Reference Manual September 2019 00809 0100 5900 182 Reference Manual ...
Page 186: ...Operation Reference Manual September 2019 00809 0100 5900 186 Reference Manual ...
Page 266: ...Product Certifications Reference Manual September 2019 00809 0100 5900 266 Reference Manual ...