3.4
Electrical installation
3.4.1
Cable/conduit entries
The electronics housing has two entries for
½
- 14 NPT. Optional M20
×
1.5, minifast and
eurofast adapters are also available. The connections must be made in accordance with
local or plant electrical codes.
Make sure that unused ports are properly sealed to prevent moisture or other
contamination from entering the terminal block compartment of the electronics housing.
Note
Use the enclosed metal plugs to seal unused ports. The plastic plugs mounted at delivery
are not sufficient as seal!
Note
Thread sealing (PTFE) tape or paste on male threads of conduit is required to provide a
water/dust tight conduit seal and to meet the required degree of ingress protection as
well as to enable future removal of the plug/gland.
NPT is a standard for tapered threads. Engage the gland with 5 to 6 threads. Note that
there will be a number of threads left outside the housing as illustrated below.
Figure 3-19: Cable Entry with NPT Threaded Gland
$
A. The NPT threaded gland leaves a number of threads outside the housing
Ensure that glands for the cable entries meet requirements for IP class 66 and 67.
3.4.2
Grounding
The housing should always be grounded in accordance with national and local electrical
codes. Failure to do so may impair the protection provided by the equipment. The most
effective grounding method is direct connection to earth ground with minimal
impedance. There are three grounding screw connections provided. Two are located
inside the terminal compartment of the housing and the third is located on the housing.
The internal ground screws are identified by a ground symbol: .
Note
Grounding the transmitter via threaded conduit connection may not provide sufficient
ground.
Reference Manual
Installation
00809-0100-5900
September 2019
Rosemount 5900S Radar Level Gauge
77
Summary of Contents for Rosemount 5900S Series
Page 1: ...Reference Manual 00809 0100 5900 Rev EA September 2019 Rosemount 5900S Radar Level Gauge ...
Page 6: ...Contents Reference Manual September 2019 00809 0100 5900 vi Reference Manual ...
Page 12: ...Introduction Reference Manual September 2019 00809 0100 5900 12 Reference Manual ...
Page 182: ...Configuration Reference Manual September 2019 00809 0100 5900 182 Reference Manual ...
Page 186: ...Operation Reference Manual September 2019 00809 0100 5900 186 Reference Manual ...
Page 266: ...Product Certifications Reference Manual September 2019 00809 0100 5900 266 Reference Manual ...