7. Choose
Manual Setup
and select the
Advanced
tab.
8. Click the
LPG Setup
button.
9. Select the
Vapor Pressure and Temperature
tab.
10. Verify that Vapor Pressure and Vapor Temperature appear in the corresponding
fields. If not, check that the devices are properly wired and the Analog Output
blocks are configured in, for example, Control Studio. In case you would like to use
manual values, click the
Change Vapor Temperature
/
Change Vapor Pressure
button and follow the method’s instructions.
Configuration
Reference Manual
September 2019
00809-0100-5900
176