CPX230NWB ALARM CONTROL PANEL – INSTALLER MANUAL
72 / 144
EN
6.3.
INPUTS / OUTPUTS
The alarm control panel has 32 configurable zones and 3 software controlled outputs.
Zones can be freely divided into two partitions. Each of zones and outputs has a number
of programmable parameters defined below.
6.3.1.
Zones (inputs)
6.3.1.1.
Zone mode
The parameter allows for determining the stable input zone state. Any change of that state
causes alarm message to be sent. Wired input can be NO or NC type. The following
configuration types are available: NO / NC / EOL-NO / EOL-NC / DEOL-NO / DEOL-NC /
Wireless / TEOL. NC type input must be closed for the whole time. Zone interruption
causes its induction. NO type input remains open. It activates when closed. EOL and DEOL
(with parameters or double parameters assigned) differ in the number of resistors allowing
to distinguish alarm from sabotage. The TEOL configuration is used to double an alarm
zone, i.e. connect two wire detectors to one clamp at the central, and it is possible to
detect alarms from detector 1 and detector 2 (see drawing 3), while signaling sabotage
switch (tamper) open will be common for both detectors.
Electric diagrams for all configuration types were described in chapter 3.4
Configuration of
wired input zones
.