CPX230NWB ALARM CONTROL PANEL – INSTALLER MANUAL
88 / 144
EN
6.4.14.
Alarm history notification disabling delay
This function is only availible after checking "After disarming disable alarm history
notification" option. It sets the delay time in seconds, after which the alarm memory will
no longer be shown on the keypad. It means, that when the system is armed, and there
will be violation of input zones shown by the F and 6 diodes blinking, then after disarming
and previously defined time the diodes will turn off. The alarm memory will still be
accessible with 3# function, until the user decides to delete it.
6.4.15.
Prevent arming using wired keypad when inputs are triggered or
sabotaged
If this option is selected, you can’t arm the system with KP32 if the detectors have been
triggered or tampered with. Triggering/tampering with any detector assigned to the
system is signalled by the diodes READY – D going off – in the case of a detector
assigned to Partition 1; 4 in the case of a detector from Partition 2. If the system has
been broken into two partitions, you can’t arm the control panel even, if the detector has
been triggered/tampered within only one of them. When attempting to arm the system,
the wired keypad emits a high one-second sound and, at the same time, the diodes
GROUP, ALARM, SYSTEM and PROG will go on for about 4 seconds. System failures do
not affect this option.
NOTE: This option is available since the firmware version 2.8.8.
6.4.16.
Time to detect loss of wireless detector
This function allows you to set the time after which a notification is sent to the monitoring
station about the loss of the wireless detector.
The time is expressed in hours. The default value is 6 hours, the minimum is 2 and the
maximum is 24.
NOTE: This option is available since the firmware version 2.8.8.
6.4.17.
Repeat every
This function allows you to switch on periodic repeating of wireless detector loss events to
the monitoring station (starting from the first loss).
The time is expressed in hours. The default value is 6 hours, the minimum is 2 and the
maximum is 24.
NOTE: This option is available since the firmware version 2.10.0.
6.4.18.
Access code length
The function enables setting the length of the administrator and user codes (the change
applies to all users). The code range is from 4 to 7 digits. By default, this value is set to 4.