Ch12 Descriptions of Parameter Settings
| VFD-ED
12-64
07 Special Parameters
: You can set this parameter during operation.
Brake Transistor Level
Control Mode
VF VFPG SVC
FOCPG FOCPM
Default:
380.0/760.0
Settings
230V series: 350.0–450.0 V
DC
460V series: 700.0–900.0 V
DC
Sets the DC bus voltage at which the brake transistor is activated.
Brake Transistor Hysteresis Voltage
Control Mode
VF VFPG SVC
FOCPG FOCPM
Default:
0.0
Settings
0.0–100.0 V
Used with Pr.07-00 to make the activated voltage level within range in order to prevent the brake resistor
from overheating due to frequent ON/OFF of the brake transistor caused by fluctuated DC bus voltage.
DC Brake Current Level at Start-up
Control Mode
VF
VFPG
SVC
Default:
0
Settings
0–100% of the rated current of the motor drive
Sets the level of the DC brake current output to the motor at start-up. When setting the DC brake current,
the rated current (Pr.00-01) is 100%. It is recommended that you start with a low DC brake current level
and then increase until you reach the proper holding torque. However, the DC brake current cannot exceed
the motor’s rated current to prevent the motor from burnout. Therefore, DO NOT use the DC brake for
mechanical retention, otherwise injury or accident may occur.
When in FOCPG/FOCPM mode, you can enable the DC brake function without setting up this parameter.
DC Brake Activation Time
Control Mode
VF VFPG SVC
FOCPG FOCPM
Default:
0.7
Settings
0.0–60.0 sec.
Sets the length of time that the DC brake current is supplied to motor when activating the drive.
DC Brake Stopping Time
Control Mode
VF VFPG SVC
FOCPG FOCPM
Default:
0.7
Settings
0.0–60.0 sec.
Sets the length of time that the DC brake current is supplied to motor when stopping the drive.
Summary of Contents for VFD-ED Series
Page 3: ......
Page 10: ...Ch01 Introduction VFD ED 1 3 1 2 Model Name 1 3 Serial Number...
Page 21: ...Ch01 Introduction VFD ED 1 14 Built In Keyboard Panel KPED LE01 Unit mm inch...
Page 26: ...Ch02 Installation VFD ED 2 5 Ambient Temperature Derating Curve Altitude Derating Curve...
Page 27: ...Ch02 Installation VFD ED 2 6 The page intentionally left blank...
Page 28: ...Ch03 Wiring VFD ED 3 1 Chapter 3 Wiring 3 1 Wiring 3 2 System Wiring Diagram...
Page 30: ...Ch03 Wiring VFD ED 3 3 3 1 Wiring...
Page 32: ...Ch03 Wiring VFD ED 3 5...
Page 38: ...Ch04 Main Circuit Terminals VFD ED 4 3 4 1 Main Circuit Diagram Frame B Frames C D Frame E...
Page 46: ...Ch05 Control Terminals VFD ED 5 3 Frame E Step 1 Step 2 Step 3...
Page 47: ...Ch05 Control Terminals VFD ED 5 4 5 2 Control Terminal Specifications...
Page 51: ...Ch05 Control Terminals VFD ED 5 8 The page intentionally left blank...
Page 94: ...06 Optional Accessories VFD ED 6 43 EMC Filter Model B84143D0150R127 Unit mm inch...
Page 95: ...06 Optional Accessories VFD ED 6 44 EMC Filter Model B84143D0200R127 Unit mm inch...
Page 96: ...06 Optional Accessories VFD ED 6 45 EMC Filter Model B84142A0042R122 Unit mm inch...
Page 242: ...Ch12 Descriptions of Parameter Settings VFD ED 12 31 Elevator Timing Diagram...
Page 313: ...Ch12 Descriptions of Parameter Settings VFD ED 12 102 The page intentionally left blank...
Page 317: ...Ch13 Warning Codes VFD ED 13 4 The page intentionally left blank...
Page 329: ...Ch14 Fault Codes VFD ED 14 12 The page intentionally left blank...
Page 351: ...Ch16 Safe Torque Off Function VFD ED 16 10 16 5 6 STL1 Figure 6 16 5 7 STL2 Figure 7...
Page 353: ...Ch16 Safe Torque Off Function VFD ED 16 12 The page intentionally left blank...
Page 373: ...Appendix A EMC Standard Installation Guide VFD ED A 20 The page intentionally left blank...
Page 389: ...Appendix B Revision History VFD ED B 16 The page intentionally left blank...