Ch12 Descriptions of Parameter Settings
| VFD-ED
12-62
When you set Pr.06-79 to 0:
Disable the operation direction count function and clear parameters (Pr.06-75, 06-76, and 06-78), and add
one time to the number of time for single operation reset (pr.06-77).
When you set Pr.06-79 to 1:
Enable the operation direction count function and add one time to the permanent operation direction count
and single operation direction count whenever the operation direction changes. If the single operation
direction count is larger than Pr.06-78, it displays a ERV warning and continues operation.
When you set Pr.06-79 to 2:
Enable the operation direction count function and add one time to the permanent operation direction count
and single operation direction count whenever the operation direction changes. If the single operation
direction count is larger than Pr.06-78, it displays a SERV warning and decelerates to stop.
Output Frequency when Fault 2 Occurred
Control Mode
VF VFPG SVC
FOCPG FOCPM
Default: Read only
Settings
0.00–655.35 Hz
DC Bus Voltage when Fault 2 Occurred
Control Mode
VF VFPG SVC
FOCPG FOCPM
Default: Read only
Settings
0.0–6553.5 V
Output Current when Fault 2 Occurred
Control Mode
VF VFPG SVC
FOCPG FOCPM
Default: Read only
Settings
0.00–655.35 Amps
IGBT Temperature when Fault 2 Occurred
Control Mode
VF VFPG SVC
FOCPG FOCPM
Default: Read only
Settings
-3276.8–3276.7ºC
Output Frequency when Fault 3 Occurred
Control Mode
VF VFPG SVC
FOCPG FOCPM
Default: Read only
Settings
0.00–655.35 Hz
DC Bus Voltage when Fault 3 Occurred
Control Mode
VF VFPG SVC
FOCPG FOCPM
Default: Read only
Settings
0.0–6553.5 V
Output Current when Fault 3 Occurred
Control Mode
VF VFPG SVC
FOCPG FOCPM
Default: Read only
Settings
0.00–655.35 Amps
IGBT Temperature when Fault 3 Occurred
Control Mode
VF VFPG SVC
FOCPG FOCPM
Default: Read only
Settings
-3276.8–3276.7ºC
Output Frequency when Fault 4 Occurred
Control Mode
VF VFPG SVC
FOCPG FOCPM
Default: Read only
Settings
0.00–655.35 Hz
DC Bus Voltage when Fault 4 Occurred
Control Mode
VF VFPG SVC
FOCPG FOCPM
Default: Read only
Settings
0.0–6553.5 V
Output Current when Fault 4 Occurred
Control Mode
VF VFPG SVC
FOCPG FOCPM
Default: Read only
Settings
0.00–655.35 Amps
Summary of Contents for VFD-ED Series
Page 3: ......
Page 10: ...Ch01 Introduction VFD ED 1 3 1 2 Model Name 1 3 Serial Number...
Page 21: ...Ch01 Introduction VFD ED 1 14 Built In Keyboard Panel KPED LE01 Unit mm inch...
Page 26: ...Ch02 Installation VFD ED 2 5 Ambient Temperature Derating Curve Altitude Derating Curve...
Page 27: ...Ch02 Installation VFD ED 2 6 The page intentionally left blank...
Page 28: ...Ch03 Wiring VFD ED 3 1 Chapter 3 Wiring 3 1 Wiring 3 2 System Wiring Diagram...
Page 30: ...Ch03 Wiring VFD ED 3 3 3 1 Wiring...
Page 32: ...Ch03 Wiring VFD ED 3 5...
Page 38: ...Ch04 Main Circuit Terminals VFD ED 4 3 4 1 Main Circuit Diagram Frame B Frames C D Frame E...
Page 46: ...Ch05 Control Terminals VFD ED 5 3 Frame E Step 1 Step 2 Step 3...
Page 47: ...Ch05 Control Terminals VFD ED 5 4 5 2 Control Terminal Specifications...
Page 51: ...Ch05 Control Terminals VFD ED 5 8 The page intentionally left blank...
Page 94: ...06 Optional Accessories VFD ED 6 43 EMC Filter Model B84143D0150R127 Unit mm inch...
Page 95: ...06 Optional Accessories VFD ED 6 44 EMC Filter Model B84143D0200R127 Unit mm inch...
Page 96: ...06 Optional Accessories VFD ED 6 45 EMC Filter Model B84142A0042R122 Unit mm inch...
Page 242: ...Ch12 Descriptions of Parameter Settings VFD ED 12 31 Elevator Timing Diagram...
Page 313: ...Ch12 Descriptions of Parameter Settings VFD ED 12 102 The page intentionally left blank...
Page 317: ...Ch13 Warning Codes VFD ED 13 4 The page intentionally left blank...
Page 329: ...Ch14 Fault Codes VFD ED 14 12 The page intentionally left blank...
Page 351: ...Ch16 Safe Torque Off Function VFD ED 16 10 16 5 6 STL1 Figure 6 16 5 7 STL2 Figure 7...
Page 353: ...Ch16 Safe Torque Off Function VFD ED 16 12 The page intentionally left blank...
Page 373: ...Appendix A EMC Standard Installation Guide VFD ED A 20 The page intentionally left blank...
Page 389: ...Appendix B Revision History VFD ED B 16 The page intentionally left blank...