Ch12 Descriptions of Parameter Settings
| VFD-ED
12-55
This parameter works with setting 43 (EPS function) for Pr.02-01–Pr.02-08 (multi-function input
commands).
Emergency Power (EPS) Mode Operation Speed
Control Mode
VF VFPG SVC
FOCPG FOCPM
Default: Read only
Settings
0.00–400.00 Hz
Emergency Power (EPS) ON Operation Direction
Control Mode
VF VFPG SVC
FOCPG FOCPM
Default:
0
Settings
0: Run according to current command
1: Run according to the operation direction of power generation mode, and execute
the power generation direction detection when in power generation mode.
2: After determining the power generation direction, the host controller sends a
running direction command. (When at STOP, the direction of power generation
mode (MO = 32) confirms and the direction of power generation mode does not
remain.) Execute the power generation direction detection every time.
3: After determining the power generation direction, the host controller sends a
running direction command. (When at STOP, the direction of power generation
mode (MO =32) confirms and the direction of power generation mode remains.)
Execute the power generation direction detection one time.
4: Run according to the operation direction of power generation mode, and execute
the power generation direction detection when in normal mode.
Pr.06-46 is enabled when the external terminal detects the emergency power signal EPS (MI=43).
When you set Pr.06-46 to 1 and a forward/reverse run command is given, the drive checks for the
elevator loading and operates in the power regeneration direction (the motor is in power generating
status). The drive uses and operates in the direction that was detected as its power regeneration
direction. For safety, the drive does not operate in user command direction to prevent emergency power
voltage drop (EPS).
When you set Pr.06-46 to 4 (motor with gear box):
1.
When the normal mode runs to the largest power factor angel, the results are saved in Pr.06-69.
2.
Compare the power factor angle detected by the power generation direction with Pr.06-86 setting
value, if the value is larger than Pr.06-68, the current direction is saved in Pr.06-70.
3.
When in emergency power mode, the drive runs according to the Pr.06-70 operation direction.
VF and SVC control modes: In the time setting in Pr.06-47, the drive detects the elevator loading status
by performing forward/reverse run. Then the elevator operates in the power regeneration direction (the
motor is in power generating status). Refer to the diagram below for the Auto-Detection Timing Graph.
Summary of Contents for VFD-ED Series
Page 3: ......
Page 10: ...Ch01 Introduction VFD ED 1 3 1 2 Model Name 1 3 Serial Number...
Page 21: ...Ch01 Introduction VFD ED 1 14 Built In Keyboard Panel KPED LE01 Unit mm inch...
Page 26: ...Ch02 Installation VFD ED 2 5 Ambient Temperature Derating Curve Altitude Derating Curve...
Page 27: ...Ch02 Installation VFD ED 2 6 The page intentionally left blank...
Page 28: ...Ch03 Wiring VFD ED 3 1 Chapter 3 Wiring 3 1 Wiring 3 2 System Wiring Diagram...
Page 30: ...Ch03 Wiring VFD ED 3 3 3 1 Wiring...
Page 32: ...Ch03 Wiring VFD ED 3 5...
Page 38: ...Ch04 Main Circuit Terminals VFD ED 4 3 4 1 Main Circuit Diagram Frame B Frames C D Frame E...
Page 46: ...Ch05 Control Terminals VFD ED 5 3 Frame E Step 1 Step 2 Step 3...
Page 47: ...Ch05 Control Terminals VFD ED 5 4 5 2 Control Terminal Specifications...
Page 51: ...Ch05 Control Terminals VFD ED 5 8 The page intentionally left blank...
Page 94: ...06 Optional Accessories VFD ED 6 43 EMC Filter Model B84143D0150R127 Unit mm inch...
Page 95: ...06 Optional Accessories VFD ED 6 44 EMC Filter Model B84143D0200R127 Unit mm inch...
Page 96: ...06 Optional Accessories VFD ED 6 45 EMC Filter Model B84142A0042R122 Unit mm inch...
Page 242: ...Ch12 Descriptions of Parameter Settings VFD ED 12 31 Elevator Timing Diagram...
Page 313: ...Ch12 Descriptions of Parameter Settings VFD ED 12 102 The page intentionally left blank...
Page 317: ...Ch13 Warning Codes VFD ED 13 4 The page intentionally left blank...
Page 329: ...Ch14 Fault Codes VFD ED 14 12 The page intentionally left blank...
Page 351: ...Ch16 Safe Torque Off Function VFD ED 16 10 16 5 6 STL1 Figure 6 16 5 7 STL2 Figure 7...
Page 353: ...Ch16 Safe Torque Off Function VFD ED 16 12 The page intentionally left blank...
Page 373: ...Appendix A EMC Standard Installation Guide VFD ED A 20 The page intentionally left blank...
Page 389: ...Appendix B Revision History VFD ED B 16 The page intentionally left blank...