Ch12 Descriptions of Parameter Settings
| VFD-ED
12-40
05 IM Parameters
: You can set this parameter during operation.
Motor Auto-tuning
Control Mode
VF
Default:
0
Settings
0: No function
1: Dynamic test (Rs, Rr, Lm, Lx, no-load current) [motor runs]
2: Static Test [motor does not run]
Position the elevator near the middle floors before auto-tuning.
Motor
auto-tuning:
Set Pr.05-00 to 1 or 2, and then press the RUN key on the digital keypad KPC-CC01 (Pr.00-15=2) to start
auto-tuning. Or when the drive is in manual mode (inspection), run the upward operation or downward
operation (Pr.00-15=1) to start auto-tuning immediately. In the process of auto-tuning, an “Auto tuning”
warning continuously displays on the digital keypad until it is finished.
Pay attention to the following notes when Pr.05-00=1 (dynamic test):
1. Make sure that all the drive parameters are set to defaults and the motor wiring is correct.
2. Make sure the motor is not loaded before auto-tuning, and that the shaft is not connected to any belt
or gear motor. Set this parameter to 2 if you cannot separate the motor from the load.
3. Enter the correct values for Pr.01-01, Pr.01-02, Pr.05-01, Pr.05-02, Pr.05-03 and Pr.05-04. Refer to
motor capacity to set the acceleration/deceleration time.
4.
After auto-tuning is finished, check if Pr.05-05
–
Pr.05-09 all have values.
5.
Equivalent circuit diagram:
NOTE
In torque/vector control mode, do not run motors in parallel.
Do not use torque/vector control mode if the motor rated power exceeds the rated power for the AC
motor drive.
The no-load current is usually 20–50% of the rated current.
The rated speed cannot be larger or equal to 120 f/p (f: output frequency Pr.01-01, p: Number of
Motor Poles Pr.05-04).
After auto-tuning is finished, activate the drive again to make it operate when the auto-tuning
command source is the external terminal.
Motor Rated Current
Control Mode
VF VFPG SVC
FOCPG
Unit:
Amp
Default: #.##
Settings
(40–120%)* Pr.00-01 Amps
Set this value according to the rated motor frequency from the motor nameplate.
Example: Suppose the rated current for 7.5 HP (5.5 kW) models is 25 A and the default is 22.5 A. In this
way, the current range is from 10 A (25 * 40%) to 30 A (25 * 120%).
As shown in the table below, the defaults vary according to the different motor drive outputs in HP and in
kW.
Summary of Contents for VFD-ED Series
Page 3: ......
Page 10: ...Ch01 Introduction VFD ED 1 3 1 2 Model Name 1 3 Serial Number...
Page 21: ...Ch01 Introduction VFD ED 1 14 Built In Keyboard Panel KPED LE01 Unit mm inch...
Page 26: ...Ch02 Installation VFD ED 2 5 Ambient Temperature Derating Curve Altitude Derating Curve...
Page 27: ...Ch02 Installation VFD ED 2 6 The page intentionally left blank...
Page 28: ...Ch03 Wiring VFD ED 3 1 Chapter 3 Wiring 3 1 Wiring 3 2 System Wiring Diagram...
Page 30: ...Ch03 Wiring VFD ED 3 3 3 1 Wiring...
Page 32: ...Ch03 Wiring VFD ED 3 5...
Page 38: ...Ch04 Main Circuit Terminals VFD ED 4 3 4 1 Main Circuit Diagram Frame B Frames C D Frame E...
Page 46: ...Ch05 Control Terminals VFD ED 5 3 Frame E Step 1 Step 2 Step 3...
Page 47: ...Ch05 Control Terminals VFD ED 5 4 5 2 Control Terminal Specifications...
Page 51: ...Ch05 Control Terminals VFD ED 5 8 The page intentionally left blank...
Page 94: ...06 Optional Accessories VFD ED 6 43 EMC Filter Model B84143D0150R127 Unit mm inch...
Page 95: ...06 Optional Accessories VFD ED 6 44 EMC Filter Model B84143D0200R127 Unit mm inch...
Page 96: ...06 Optional Accessories VFD ED 6 45 EMC Filter Model B84142A0042R122 Unit mm inch...
Page 242: ...Ch12 Descriptions of Parameter Settings VFD ED 12 31 Elevator Timing Diagram...
Page 313: ...Ch12 Descriptions of Parameter Settings VFD ED 12 102 The page intentionally left blank...
Page 317: ...Ch13 Warning Codes VFD ED 13 4 The page intentionally left blank...
Page 329: ...Ch14 Fault Codes VFD ED 14 12 The page intentionally left blank...
Page 351: ...Ch16 Safe Torque Off Function VFD ED 16 10 16 5 6 STL1 Figure 6 16 5 7 STL2 Figure 7...
Page 353: ...Ch16 Safe Torque Off Function VFD ED 16 12 The page intentionally left blank...
Page 373: ...Appendix A EMC Standard Installation Guide VFD ED A 20 The page intentionally left blank...
Page 389: ...Appendix B Revision History VFD ED B 16 The page intentionally left blank...