06 Optional Accessories | VFD-ED
6-35
Reactor
Model
(See Note)
Recommended Wire Size
Wiring
Method
Qty
Applicable Motor Drives
RF008X00A
T60006L2040W453
≤
8 AWG
≤
8.37 mm
2
Diagram A
Diagram B
1
VFD022ED21S VFD037ED21S
VFD040ED23S VFD040ED43S
RF004X00A
T60006L2050W565
≤
4 AWG
≤
21.15 mm
2
Diagram A
Diagram B
1
VFD055ED23S VFD075ED23S
VFD110ED23S VFD055ED43S
VFD075ED43S VFD110ED43S
VFD150ED43S VFD185ED43S
RF002X00A
T60006L2160V066
≤
2 AWG
≤
33.62 mm
2
Diagram A
Diagram B
1
VFD150ED23S VFD185ED23S
VFD220ED23S VFD220ED43S
VFD300ED43S
RF300X00A
T60006L2160V066
≤
300 MCM
≤
152 mm
2
Diagram A
Diagram B
1
VFD300ED23S VFD370ED23S
VFD370ED43S VFD450ED43S
VFD550ED43S VFD750ED43S
Note:
600 V insulated cable wire
Installation
During installation, pass the cable through at least one zero phase reactor. Use a suitable cable type
(insulation class and wire section) so that the cable passes easily through the zero phase reactor. Do not
pass the grounding cable through the zero phase reactor; only pass the motor wire through the zero
phase reactor. With longer motor cables the zero-phase reactor can effectively reduce interference at the
motor output. Install the zero-phase reactor as close to the output of the drive as possible. Diagram A
shows the installation diagram for a single turn zero phase reactor. If the wire diameter allows several
turns, Diagram B shows the installation of a multi-turn zero phase reactor. The more turns, the better the
noise suppression effect.
Diagram A. Single turn wiring diagram for shielding wire with a zero phase reactor
Diagram B. Multi-turn zero phase reactor
Summary of Contents for VFD-ED Series
Page 3: ......
Page 10: ...Ch01 Introduction VFD ED 1 3 1 2 Model Name 1 3 Serial Number...
Page 21: ...Ch01 Introduction VFD ED 1 14 Built In Keyboard Panel KPED LE01 Unit mm inch...
Page 26: ...Ch02 Installation VFD ED 2 5 Ambient Temperature Derating Curve Altitude Derating Curve...
Page 27: ...Ch02 Installation VFD ED 2 6 The page intentionally left blank...
Page 28: ...Ch03 Wiring VFD ED 3 1 Chapter 3 Wiring 3 1 Wiring 3 2 System Wiring Diagram...
Page 30: ...Ch03 Wiring VFD ED 3 3 3 1 Wiring...
Page 32: ...Ch03 Wiring VFD ED 3 5...
Page 38: ...Ch04 Main Circuit Terminals VFD ED 4 3 4 1 Main Circuit Diagram Frame B Frames C D Frame E...
Page 46: ...Ch05 Control Terminals VFD ED 5 3 Frame E Step 1 Step 2 Step 3...
Page 47: ...Ch05 Control Terminals VFD ED 5 4 5 2 Control Terminal Specifications...
Page 51: ...Ch05 Control Terminals VFD ED 5 8 The page intentionally left blank...
Page 94: ...06 Optional Accessories VFD ED 6 43 EMC Filter Model B84143D0150R127 Unit mm inch...
Page 95: ...06 Optional Accessories VFD ED 6 44 EMC Filter Model B84143D0200R127 Unit mm inch...
Page 96: ...06 Optional Accessories VFD ED 6 45 EMC Filter Model B84142A0042R122 Unit mm inch...
Page 242: ...Ch12 Descriptions of Parameter Settings VFD ED 12 31 Elevator Timing Diagram...
Page 313: ...Ch12 Descriptions of Parameter Settings VFD ED 12 102 The page intentionally left blank...
Page 317: ...Ch13 Warning Codes VFD ED 13 4 The page intentionally left blank...
Page 329: ...Ch14 Fault Codes VFD ED 14 12 The page intentionally left blank...
Page 351: ...Ch16 Safe Torque Off Function VFD ED 16 10 16 5 6 STL1 Figure 6 16 5 7 STL2 Figure 7...
Page 353: ...Ch16 Safe Torque Off Function VFD ED 16 12 The page intentionally left blank...
Page 373: ...Appendix A EMC Standard Installation Guide VFD ED A 20 The page intentionally left blank...
Page 389: ...Appendix B Revision History VFD ED B 16 The page intentionally left blank...