Ch12 Descriptions of Parameter Settings
| VFD-ED
12-59
If STO is ON in any condition and a fault occurs, it does not reset until STO is back to normal and use a
RESET command or power-on again after resending the RUN command.
0001h: STO warning latched, resending RUN command is required
If STO is ON in any condition and a warning occurs, it does not reset until STO is back to normal and
resend the RUN command.
0002h: STO fault latched
If STO is ON in any condition and a fault occurs, it does not reset until STO is back to normal and use a
RESET command or power-on again.
0003h: STO warning unlatched
If STO is ON in any condition and a warning occurs, it automatically resets when STO is back to normal.
For more information on the timing diagram, see Section 16-5.
Make sure there is no risk, which is assessed by the elevator controller, before using the STO warning
unlatched function.
Fault codes STL1 to STL3 are regarded as fault latched (you cannot set Pr.06-49).
MO’s Action when Retrying after Fault
Control Mode
VF VFPG SVC
FOCPG FOCPM
Default:
0
Settings
0: Output
1: No output
Determines whether to display the fault indication when the following faults occur:
7: Over-voltage during acceleration (ovA)
8: Over-voltage during deceleration (ovd)
9: Over-voltage during constant speed (ovn)
10: Over-voltage at stop (ovS)
11: Low voltage during acceleration (LvA)
12: Low voltage during deceleration (Lvd)
13: Low voltage during constant speed (Lvn)
14: Low voltage at stop (LvS)
15: Input Phase loss (PHL)
Two MO terminals are affected by this parameter and should be set up as:
MO = 10: Low voltage waning (LV)
MO = 11: Fault Indication
Number of Times to Retry after Fault
Control Mode
VF VFPG SVC
FOCPG FOCPM
Default:
0
Settings
0–10 times
To determine the number of times to retry when the following faults occur:
7: Over-voltage during acceleration (ovA)
8: Over-voltage during deceleration (ovd)
9: Over-voltage during constant speed (ovn)
10: Over-voltage at stop (ovS)
11: Low voltage during acceleration (LvA)
12: Low voltage during deceleration (Lvd)
13: Low voltage during constant speed (Lvn)
14: Low voltage at stop (LvS)
15: Input Phase loss (PHL)
After every retry attempt, the number of times to retry is automatically reduced by one as displayed on the
keypad.
The principles for the number of times to reset:
1. Reset the fault manually.
2. After running normally for 10 minutes, the motor drive returns to the prior setting.
3. The motor drive is powered on and powered off again.
Summary of Contents for VFD-ED Series
Page 3: ......
Page 10: ...Ch01 Introduction VFD ED 1 3 1 2 Model Name 1 3 Serial Number...
Page 21: ...Ch01 Introduction VFD ED 1 14 Built In Keyboard Panel KPED LE01 Unit mm inch...
Page 26: ...Ch02 Installation VFD ED 2 5 Ambient Temperature Derating Curve Altitude Derating Curve...
Page 27: ...Ch02 Installation VFD ED 2 6 The page intentionally left blank...
Page 28: ...Ch03 Wiring VFD ED 3 1 Chapter 3 Wiring 3 1 Wiring 3 2 System Wiring Diagram...
Page 30: ...Ch03 Wiring VFD ED 3 3 3 1 Wiring...
Page 32: ...Ch03 Wiring VFD ED 3 5...
Page 38: ...Ch04 Main Circuit Terminals VFD ED 4 3 4 1 Main Circuit Diagram Frame B Frames C D Frame E...
Page 46: ...Ch05 Control Terminals VFD ED 5 3 Frame E Step 1 Step 2 Step 3...
Page 47: ...Ch05 Control Terminals VFD ED 5 4 5 2 Control Terminal Specifications...
Page 51: ...Ch05 Control Terminals VFD ED 5 8 The page intentionally left blank...
Page 94: ...06 Optional Accessories VFD ED 6 43 EMC Filter Model B84143D0150R127 Unit mm inch...
Page 95: ...06 Optional Accessories VFD ED 6 44 EMC Filter Model B84143D0200R127 Unit mm inch...
Page 96: ...06 Optional Accessories VFD ED 6 45 EMC Filter Model B84142A0042R122 Unit mm inch...
Page 242: ...Ch12 Descriptions of Parameter Settings VFD ED 12 31 Elevator Timing Diagram...
Page 313: ...Ch12 Descriptions of Parameter Settings VFD ED 12 102 The page intentionally left blank...
Page 317: ...Ch13 Warning Codes VFD ED 13 4 The page intentionally left blank...
Page 329: ...Ch14 Fault Codes VFD ED 14 12 The page intentionally left blank...
Page 351: ...Ch16 Safe Torque Off Function VFD ED 16 10 16 5 6 STL1 Figure 6 16 5 7 STL2 Figure 7...
Page 353: ...Ch16 Safe Torque Off Function VFD ED 16 12 The page intentionally left blank...
Page 373: ...Appendix A EMC Standard Installation Guide VFD ED A 20 The page intentionally left blank...
Page 389: ...Appendix B Revision History VFD ED B 16 The page intentionally left blank...