Ch12 Descriptions of Parameter Settings
| VFD-ED
12-54
PTC Detection Filter Time
Control Mode
VF VFPG SVC
FOCPG FOCPM
Default:
0.20
Settings
0.00–10.00 sec.
See Parameter Group 03 Analog Input/ Output Parameters for details.
Phase Loss Detection of Drive Output at Start-up (MPHL)
Control Mode
VF VFPG SVC
FOCPG FOCPM
Default:
1
Settings
0: Disable
1: Enable
1: Auto-detect whether the connection between the drive and motor is normal whenever the drive runs. If
an error occurs to the connection between the drive and the motor (broken or loose wiring) or there is no
output for the drive’s any or all of the three phases, the drive displays fault code “67” to indicate motor
output phase loss.
Accumulated Drive Power-on Time at the First Fault (min.)
Accumulated Drive Power-on Time at the Second Fault (min.)
Accumulated Drive Power-on Time at the Third Fault (min.)
Accumulated Drive Power-on Time at the Fourth Fault (min.)
Accumulated Drive Power-on Time at the Fifth Fault (min.)
Accumulated Drive Power-on Time at the Sixth Fault (min.)
Control Mode
VF VFPG SVC
FOCPG
Default: Read only
Settings
0–65535 min.
Accumulated Drive Power-on Time at the First Fault (day)
Accumulated Drive Power-on Time at the Second Fault (day)
Accumulated Drive Power-on Time at the Third Fault (day)
Accumulated Drive Power-on Time at the Fourth Fault (day)
Accumulated Drive Power-on Time at the Fifth Fault (day)
Accumulated Drive Power-on Time at the Sixth Fault (day)
Control Mode
VF VFPG SVC
FOCPG
Default: Read only
Settings
0–65535 day
Fault and Warning Action
Control Mode
VF VFPG SVC
FOCPG FOCPM
Default:
0
Settings
Bit 0 = 0: Display Lv fault and coast to stop
Bit 0 = 1: Display Lv warn and coast to stop
Bit 1= 0 : Fan lock, fault and coast to stop
Bit 1 = 1: Fan lock, warn and coast to stop
Bit 2 = 0: Software GFF protection enabled
Bit 2 = 1: Software GFF protection disabled
Voltage of Emergency Power
Control Mode
VF VFPG SVC
FOCPG FOCPM
Default:
24.0/48.0
Settings
24.0–375.0 V
DC
48.0–750.0 V
DC
Summary of Contents for VFD-ED Series
Page 3: ......
Page 10: ...Ch01 Introduction VFD ED 1 3 1 2 Model Name 1 3 Serial Number...
Page 21: ...Ch01 Introduction VFD ED 1 14 Built In Keyboard Panel KPED LE01 Unit mm inch...
Page 26: ...Ch02 Installation VFD ED 2 5 Ambient Temperature Derating Curve Altitude Derating Curve...
Page 27: ...Ch02 Installation VFD ED 2 6 The page intentionally left blank...
Page 28: ...Ch03 Wiring VFD ED 3 1 Chapter 3 Wiring 3 1 Wiring 3 2 System Wiring Diagram...
Page 30: ...Ch03 Wiring VFD ED 3 3 3 1 Wiring...
Page 32: ...Ch03 Wiring VFD ED 3 5...
Page 38: ...Ch04 Main Circuit Terminals VFD ED 4 3 4 1 Main Circuit Diagram Frame B Frames C D Frame E...
Page 46: ...Ch05 Control Terminals VFD ED 5 3 Frame E Step 1 Step 2 Step 3...
Page 47: ...Ch05 Control Terminals VFD ED 5 4 5 2 Control Terminal Specifications...
Page 51: ...Ch05 Control Terminals VFD ED 5 8 The page intentionally left blank...
Page 94: ...06 Optional Accessories VFD ED 6 43 EMC Filter Model B84143D0150R127 Unit mm inch...
Page 95: ...06 Optional Accessories VFD ED 6 44 EMC Filter Model B84143D0200R127 Unit mm inch...
Page 96: ...06 Optional Accessories VFD ED 6 45 EMC Filter Model B84142A0042R122 Unit mm inch...
Page 242: ...Ch12 Descriptions of Parameter Settings VFD ED 12 31 Elevator Timing Diagram...
Page 313: ...Ch12 Descriptions of Parameter Settings VFD ED 12 102 The page intentionally left blank...
Page 317: ...Ch13 Warning Codes VFD ED 13 4 The page intentionally left blank...
Page 329: ...Ch14 Fault Codes VFD ED 14 12 The page intentionally left blank...
Page 351: ...Ch16 Safe Torque Off Function VFD ED 16 10 16 5 6 STL1 Figure 6 16 5 7 STL2 Figure 7...
Page 353: ...Ch16 Safe Torque Off Function VFD ED 16 12 The page intentionally left blank...
Page 373: ...Appendix A EMC Standard Installation Guide VFD ED A 20 The page intentionally left blank...
Page 389: ...Appendix B Revision History VFD ED B 16 The page intentionally left blank...