Ch12 Descriptions of Parameter Settings
| VFD-ED
12-42
Lm of Motor
Lx of Motor
Control Mode
SVC
FOCPG
Default:
0.0
Settings
0.0–6553.5 mH
Torque Compensation Low Pass Filter Time
Control Mode
SVC
Default:
0.020
Settings
0.001–10.000 sec.
Slip Compensation Low Pass Filter Time
Control Mode
SVC
Default:
0.100
Settings
0.001–10.000 sec.
Setting Pr.05-10 and Pr.05-11 changes the response time for the compensation.
When you set Pr.05-10 and Pr.05-11 to 10 seconds, it maximizes the response time for the compensation.
If the settings are too low, the system may become unstable.
Torque Compensation Gain
Control Mode
VF VFPG
Default:
0
Settings
0–10
You can set this parameter so that the AC motor drive increases its voltage output for a higher torque.
Slip Compensation Gain
Control Mode
SVC
Default:
1.00
Settings
0.00–10.00
When the motor drive controls an asynchronous motor, the load and slip increase. Use this parameter to
correct the frequency and lower the slip to make the motor run near the synchronous speed under the rated
current. When the output current is larger than the motor no-load current, the drive compensates the
frequency according to the Pr.05-13 setting. If the actual speed is slower than the expected speed,
increase the setting and vice versa.
This is only valid in SVC mode.
Slip Deviation Level
Control Mode
VFPG
SVC
FOCPG
Default:
0
Settings
0–1000%
0: Disable
Slip Deviation Detection Time
Control Mode
VFPG
SVC
FOCPG
Default:1.0
Settings
0.0–10.0 sec.
Over-slip Action
Control Mode
VFPG
SVC
FOCPG
Default:
0
Settings
0: Warn and keep operation
1: Fault and ramp to stop
2: Fault and coast to stop
Pr.05-14–Pr.05-16 set the allowable slip level and over-slip action when the drive is running.
Summary of Contents for VFD-ED Series
Page 3: ......
Page 10: ...Ch01 Introduction VFD ED 1 3 1 2 Model Name 1 3 Serial Number...
Page 21: ...Ch01 Introduction VFD ED 1 14 Built In Keyboard Panel KPED LE01 Unit mm inch...
Page 26: ...Ch02 Installation VFD ED 2 5 Ambient Temperature Derating Curve Altitude Derating Curve...
Page 27: ...Ch02 Installation VFD ED 2 6 The page intentionally left blank...
Page 28: ...Ch03 Wiring VFD ED 3 1 Chapter 3 Wiring 3 1 Wiring 3 2 System Wiring Diagram...
Page 30: ...Ch03 Wiring VFD ED 3 3 3 1 Wiring...
Page 32: ...Ch03 Wiring VFD ED 3 5...
Page 38: ...Ch04 Main Circuit Terminals VFD ED 4 3 4 1 Main Circuit Diagram Frame B Frames C D Frame E...
Page 46: ...Ch05 Control Terminals VFD ED 5 3 Frame E Step 1 Step 2 Step 3...
Page 47: ...Ch05 Control Terminals VFD ED 5 4 5 2 Control Terminal Specifications...
Page 51: ...Ch05 Control Terminals VFD ED 5 8 The page intentionally left blank...
Page 94: ...06 Optional Accessories VFD ED 6 43 EMC Filter Model B84143D0150R127 Unit mm inch...
Page 95: ...06 Optional Accessories VFD ED 6 44 EMC Filter Model B84143D0200R127 Unit mm inch...
Page 96: ...06 Optional Accessories VFD ED 6 45 EMC Filter Model B84142A0042R122 Unit mm inch...
Page 242: ...Ch12 Descriptions of Parameter Settings VFD ED 12 31 Elevator Timing Diagram...
Page 313: ...Ch12 Descriptions of Parameter Settings VFD ED 12 102 The page intentionally left blank...
Page 317: ...Ch13 Warning Codes VFD ED 13 4 The page intentionally left blank...
Page 329: ...Ch14 Fault Codes VFD ED 14 12 The page intentionally left blank...
Page 351: ...Ch16 Safe Torque Off Function VFD ED 16 10 16 5 6 STL1 Figure 6 16 5 7 STL2 Figure 7...
Page 353: ...Ch16 Safe Torque Off Function VFD ED 16 12 The page intentionally left blank...
Page 373: ...Appendix A EMC Standard Installation Guide VFD ED A 20 The page intentionally left blank...
Page 389: ...Appendix B Revision History VFD ED B 16 The page intentionally left blank...