Appendix B Modbus TCP Communication
B_
B.3
Exception Response Code in Modbus TCP
Modbus exception response codes that DVP15MC11T supports are shown in the table below.
Exception response code
Indication
0x01
Unsupportive function code
0x02
Unsupportive Modbus address
0x03
Data length exceeds the range
B.4
Modbus Function Codes in Modbus
TCP
Function code: 03 to read one single or multiple word register values
Request message data structure:
Byte NO.
Name
Byte
Byte0
Transaction identifier
High byte
Byte1
Low byte
Byte2
Protocol identifier
High byte
Byte3
Low byte
Byte4
Modbus data length
High byte
Byte5
Low byte
Byte6
Modbus ID
Low byte
Byte7
Function code
Single byte
Byte8
The start address of word registers to be
read
High byte
Byte9
Low byte
Byte10
The number of word registers
(Counted by Word)
High byte
Byte11
Low byte
Response message data structure:
Byte NO.
Name
Byte
Byte0
Transaction identifier
High byte
Byte1
Low byte
Byte2
Protocol identifier
High byte
Byte3
Low byte
Byte4
Modbus data length
High byte
Byte5
Low byte
Byte6
Modbus ID
Single byte
Byte7
Function code
Single byte
B-3
Summary of Contents for DVP15MC11T
Page 9: ...Memo viii...
Page 15: ...DVP15MC11T Operation Manual _2 MEMO 2 4...
Page 71: ...DVP15MC11T Operation Manual _7 Memo 7 10...
Page 81: ...DVP15MC11T Operation Manual _8 Timing Chart F_TRG_CLK F_TRG_Q 8 10...
Page 158: ...Chapter 8 Logic Instructions 8_ The program 1 ASIN EN ENO In Out ASIN_EN ASIN_In Out1 8 87...
Page 249: ...DVP15MC11T Operation Manual _8 8 178...
Page 285: ...DVP15MC11T Operation Manual _8 Memo 8 214...
Page 323: ...DVP15MC11T Operation Manual 10 MEMO 10 34...
Page 549: ...DVP15MC11T Operation Manual A MEMO A 16...