DVP15MC11T Operation Manual
_6
6.9
CANopen Communication Port
6.9.1
Functions that CANopen Communication Port Supports
CANopen communication port can be used as CANopen network master or as a slave of other master.
As a master, CAN1 communication port supports following functions.
Standard CANopen protocol DS301V4.02;
NMT (Network Management Object) Master service;
NMT Error control;
NMT error control is used to watch if some slave is offline. NMT error control includes Heartbeat and
Node Guarding. The module supports Heartbeat function.
Connects max. 32 slaves.
PDO (Process Data Object) service.
The number of RxPDOs: max. 200, data length: max. 1000 bytes
The number of TxPDOs: max. 200, data length: max. 1000 bytes
Maximum 8 TxPDOs and 8 RxPDOs are configured for each slave.
PDO transmission type: supporting event trigger, time trigger, synchronous and cyclic, synchronous
and acyclic
PDO mapping: every PDO can map 32 parameters at most.
The data type that CAN communication port supports
Storage capacity
Data type
1bit
BOOL
8bit
SINT, USINT,BYTE
16bit
INT, UINT, WORD
32bit
DINT, UDINT, REAL, DWORD
64bit
LINT, ULINT, LREAL, LWORD
Supports SDO service
Supports standard expedited SDO transmission mode;
Supports Auto SDO function; capable of sending a maximum of 30 Auto SDOs to each slave;
Supports reading and writing of slave data by using SDO service in PLC ladder diagram program.
SYNC producer, range 0-65535ms
Multiple devices perform an action synchronously through SYNC message.
As the connection interface between Delta CANopen Builder configuration software and
CANopen network, the configuration software can be directly used to configure the network through
DVPCOPM-SL module
Supports the CANopen communication speeds: 20K, 50K, 125K, 250K, 500K, 1Mbps
As a slave, CAN1 communication port supports following functions.
Standard CANopen protocol DS301V4.02
NMT slave service
NMT Error control
Supporting Heartbeat Protocol error control instead of Node Guarding error control
PDO service
The number of RxPDOs: max. 8, data length: max. 64 bytes
The number of TxPDOs: max .8, data length: max. 64 bytes
PDO transmission type: event trigger, time trigger, synchronous and cyclic, synchronous and acyclic
SDO service
Supporting standard expedited SDO transmission mode.
6-20
Summary of Contents for DVP15MC11T
Page 9: ...Memo viii...
Page 15: ...DVP15MC11T Operation Manual _2 MEMO 2 4...
Page 71: ...DVP15MC11T Operation Manual _7 Memo 7 10...
Page 81: ...DVP15MC11T Operation Manual _8 Timing Chart F_TRG_CLK F_TRG_Q 8 10...
Page 158: ...Chapter 8 Logic Instructions 8_ The program 1 ASIN EN ENO In Out ASIN_EN ASIN_In Out1 8 87...
Page 249: ...DVP15MC11T Operation Manual _8 8 178...
Page 285: ...DVP15MC11T Operation Manual _8 Memo 8 214...
Page 323: ...DVP15MC11T Operation Manual 10 MEMO 10 34...
Page 549: ...DVP15MC11T Operation Manual A MEMO A 16...