Outdoor Unit
SiBE12-908
251
Removal Procedure
5
Remove the 2 nuts with
an open-end spanner.
Warning
Since it may happen that
refrigerant oil in the
compressor catches fire,
prepare wet cloth so as to
extinguish fire immediately.
Warning
Ventilate when refrigerant
leaks during the work.
(If refrigerant contacts fire, it
causes to arise toxic gas.)
Warning
Be careful about the four way
valve, pipes and so on, which
were heated up by a gas
brazing machine, so as not to
get burnt your hands.
Caution
From the viewpoint of global
environment protection, do
not discharge the refrigerant
gas in the atmosphere. Make
sure to recover the refrigerant
gas with the recovery system.
Before working, make
sure that the refrigerant is
empty in the circuit.
Be sure to apply nitrogen
replacement when
heating up the brazed
part.
6
Heat up the brazed part
of the discharge side
and disconnect.
7
Heat up the brazed part
of the suction side and
disconnect.
8
Lift the compressor up
to remove.
Step
Procedure
Points
(R9989)
(R9990)
(R9991)
Compressor