![background image](http://html.mh-extra.com/html/daikin/2mxu40gv1b/2mxu40gv1b_service-manual_501101226.webp)
Outdoor Unit
SiBE12-908
215
Removal Procedure
5
Disconnect the 4 relay
connectors.
Do not pull the harnesses
from the outdoor unit
strongly so as not to loose
the hook of the mounting
plate.
(See the illustration below
on this page for the
mounting plate.)
6
Disconnect the
connector for humidifier
fan motor.
Be sure to wait 10 minutes
or more after turning off the
power supply before
disconnecting the
connectors.
Pull out the connector while
pushing up the hook on the
bottom side.
When lifting up the
humidifier unit, be careful
not to pull the relay
harnesses forcibly.
When reassembling the
humidifier unit, make sure
the mounting plate is
hooked (refer to page 232 )
and do not forget to connect
the relay connectors.
7
Remove the 4 screws
of the humidifier unit
and lift it up to remove.
Step
Procedure
Points
(R9886)
Relay connectors
(R9887)
Humidifier
fan motor
<From the back side>
}
(R9888)
Humidifier unit
Mounting plate
Hook