Troubleshooting
SiBE12-908
137
Service Diagnosis
Troubleshooting
Check No.03
Refer to P.170
Check No.11
Refer to P.171
Check No.14
Refer to P.173
Check No.16
Refer to P.175
(R9441)
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Is the current value
more than the set
stop input current
value?
YES
∗
Input over current may be caused by improper wiring inside the unit. If the
unit stops due to input over current after connecting or disconnecting wires to
replace part, check wiring for proper connection.
Get restarted and measure the
input current
NO
Check No. 11
Main circuit electrolytic
capacitor check
NO
Is it OK?
Turn off the power supply, and
disconnect U, V, and W harnesses
Check No.14
Check the inverter by the
inverter checker*
Is LED turned off?
Turn off the power supply, replace
the harnesses, and restart the
compressor after turning on the
power supply again.
Check No. 16
Discharge pressure check
Check No. 03
Installation condition check
NO
YES
Replace the outdoor unit
PCB.
Replace electrolytic
capacitor.
*Inverter checker
Part No.: 1225477
Rectify the power supply
or replace the outdoor unit
PCB.